Environmental conditions
Climate
Storage
EN 60721-3-1:1997
1K3 (-30 ... +60°C)
<3 months
1K3 (-30 ... +40 °C)
>3 months
Transport
EN 60721-3-2:1997
2K3 (-30 ...+70 °C)
Operation
EN 60721-3-3:1995 +
A2:1997
3K3 (-30 ...+40 °C)
Operation
Site altitude
0 … 1000 m amsl
-
Without current derating
1000 … 4000 m amsl
Reduce rated output current by 5 %/1000 m
Pollution
-
EN IEC 61800-5-1
Degree of pollution 2
Vibration resistance
Operation
EN 60721-3-3:1995 +
A2:1997
3M4
Transport
EN 60721-3-2:1997
2M2
Vibration severity
A
EN IEC 60034-14
-
-
Electrical supply conditions
Possibility of connection to different types of mains power supply enables worldwide use.
The following is supported:
•
3-phase mains connection 400 V
•
3-phase mains connection 480 V
Type of mains power supply
TT
Mains power supplies with earthed start point
Voltage against earth: max. 300 V
TN
Technical data
Standards and operating conditions