Parameter overview lists in this documentation
•
Keypad parameter list
: for the parameterisation using the keypad, contains a list of all
parameters which can also be accessed by means of the keypad.
^
24
•
Parameter attribute list
: contains a list of all inverter parameters. This list in particular
includes some information that is relevant for the reading and writing of parameters via the
network.
^
229
4.4.2
Basic inverter settings
Check the following basic settings of the inverter and adapt them, if required.
Parameter
Name / value range / [default setting]
Info
0x2540:001
(PAR 208/001)
Mains voltage: Rated mains voltage
(Mains volt. sett.: AC input volt.)
•
Setting can only be changed if controller inhibit is
active.
Selection of the mains voltage for actuating the inverter.
0 230 Veff
1 400 Veff
2 480 Veff
0x2838:001
(PAR 203/001)
Start/stop configuration: Start method
(Start/stop confg: Start method)
•
Setting can only be changed if controller inhibit is
active.
Starting performance of the inverter.
0 Normal
After switch-on, the standard ramps are active.
•
Acceleration time 1 can be set in
0x2917 (PAR 220)
.
•
Deceleration time 1 can be set in
0x2918 (PAR 221)
.
1 Start with DC braking
After switch-on, the "DC braking" function is active for the time set in
0x2B84:002 (PAR 704/002)
.
4
DC braking
^
153
2 Flying Start
After switch-on, the "Restart on the fly" function is active.
This function makes it possible to restart a coasting motor on the fly dur-
ing operation without speed feedback. Synchronicity between the inver-
ter and the motor is coordinated so that the transition to the rotating
drive is effected without jerk at the time of connection.
4
Flying restart function
^
182
0x2838:002
(PAR 203/002)
Start/stop configuration: Start at switch-on
(Start/stop confg: Start at switch-on)
Behaviour after mains connection.
0 Off
If the controller is enabled at mains power-up, the inverter remains in
the "Ready to switch on" state.
For a change-over to the "Switched on" state, controller enable must be
deactivated first. Only with the following controller enable, a change-
over to the "Operation enabled" state is effected, and the motor follows
the setpoint specified.
1 On
If the controller is enabled at mains power-up, after mains power-up the
motor directly follows the setpoint specified.
With this setting, the inverter directly changes from the "Ready to switch
on" state to the "Switched on" state and then to the "Operation
enabled" state.
0x2838:003
(PAR 203/003)
Start/stop configuration: Stop method
(Start/stop confg: Stop method)
Behaviour after the "Stop" command.
0 Coasting
The motor coasts down to standstill.
1 Standard Ramp
The motor is brought to a standstill with deceleration time 1 (or deceler-
ation time 2, if activated).
•
Deceleration time 1 can be set in
0x2918 (PAR 221)
.
•
Deceleration time 2 can be set in
0x291A (PAR 223)
.
4
Frequency limits and ramp times
^
73
2 Quick stop ramp
The motor is brought to a standstill with the deceleration time set for
the "Quick stop" function.
•
Deceleration time for quick stop can be set in
0x291C (PAR 225)
.
Commissioning
Parameter setting
Basic inverter settings
18