6.6
Quick stop
Parameter
Name / value range / [default setting]
Info
0x291C
(PAR 225)
Quick stop deceleration time
(QSP dec. time)
0.0 ... [1.0] ... 3600.0 s
If the "Quick stop" function is activated, the motor is brought to a stand-
still within the deceleration time set here.
The deceleration time set refers to the deceleration from the maximum
frequency set to standstill. In the case of a lower actual frequency, the
actual deceleration time is reduced accordingly.
0x2631:003
(PAR 400/003)
Function assignment: Quick stop
(Function list: Quick stop)
•
Setting can only be changed if controller inhibit is
active.
•
For possible settings see description for
0x2631:001 (PAR 400/001)
.
^
188
Assignment of a trigger for the "Quick stop" function.
Trigger = TRUE: "Quick stop" function activated.
Trigger = FALSE: no action / deactivate function again.
Notes:
•
The "Quick stop" function brings the motor to a standstill within the
deceleration time set in
0x291C (PAR 225)
.
•
The "Quick stop" function has a higher priority than the "Start enable"
function.
00 Not connected
No trigger assigned (trigger is constantly FALSE).
Basic setting
Quick stop
74
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: info@actechdrives.com