Fuse data (F1 ... F3)
Motor
MSEMA
☐☐
063-42
MSEMA
☐☐
080-32
Cable installation in compli-
ance with
UL 61800-5-1
Fuse
Standard
UL 248
Typ. rated current
A
3
6
Max. rated current
A
3
10
Semiconductor fuse
Standard
UL 248
Typ. rated current
A
3
6
Max. rated current
A
3
10
Circuit breaker
Standard
UL 489
Typ. rated current
A
15
15
Max. rated current
A
15
15
Connection for group drive according to UL 61800-5-1
L1
L2
L3
N
PE
F1 … F3
K
M
3~
+
A
1
I
N1
PE L1 L2 L3
M
3~
+
A
2
I
N2
PE L1 L2 L3
M
3~
+
A
3
I
N3
PE L1 L2 L3
M
3~
+
A
4
I
N4
PE L1 L2 L3
M
3~
+
A
n
I
Nn
PE L1 L2 L3
WARNING!
▶
UL marking
▶
Suitable for motor group installation on a circuit capable of delivering not more than 5k rms symmetrical
amperes, 480 V maximum.
▶
When protected by fuses rated, see table below.
▶
When protected by a circuit breaker having an interrupting rating not less than 5k rms symmetrical
amperes, 480 V Maximum, see table below.
▶
Marquage UL
▶
Convient aux circuits de groupes moteur non susceptibles de délivrer plus de 5k ampères symétriques eff,
maximum 480 V.
▶
Avec une protection par des fusibles du calibre indiqué dans le tableau ci-dessous,
▶
Avec une protection par un disjoncteur à courant de coupure assigné d’au moins 5k ampères symétriques
eff, maximum 480 V, voir tableau ci-dessous.
Electrical installation
Mains connection
Connection according to UL
65