EMC data
Actuation on public supply systems
Implement measures to limit the radio
interference to be expected:
The machine or plant manufacturer is responsible for com-
pliance with the requirements for the machine/plant!
< 1 kW: with mains choke
EN 61000-3-2
> 1 kW at mains current ≤ 16 A: without
additional measures
Mains current > 16 A: with mains choke or
mains filter, with dimensioning for rated
power. Rsce ≥ 120 is to be met.
EN 61000-3-12
RSCE: short-circuit power ratio at the connection point of
the machine/plant to the public network.
Noise emission
Category C2
EN 61800-3
Noise immunity
Meets requirement in compliance with
EN 61800-3
Environmental conditions
Climate
1K3 ( -30 °C ... +60 °C)
EN 60721-3-1
Storage, < 3 months
1K3 ( -30 °C ... +40 °C)
EN 60721-3-1
Storage, > 3 months
2K3 ( -30 °C ... +70 °C)
EN 60721-3-2
Transport
3K3 ( -30 °C ... +40 °C)
In the case of very low-temperature appli-
cations without condensation
EN 60721-3-3
operation
Site altitude
0 … 1000 m a.m.s.l.
Without power reduction
1000 … 4000 m a.m.s.l.
Reduce rated output current by 5 %/1000 m
Degree of pollution
Degree of pollution 2
EN 61800-5-1
Vibration resistance
2M2
EN 60721-3-2
Transport
3M4
EN 60721-3-3
operation
Vibration severity
A
EN 60034-14
Electrical supply conditions
Possibility of connection to different types of mains power supply enables worldwide use.
The following is supported:
•
3-phase mains connection 400 V
•
3-phase mains connection 480 V
Type of mains power supply
TT
Mains power supplies with earthed start point
Voltage against earth: max. 300 V
TN
Rated data
Motor
MSEMA
☐☐
063-42
MSEMA
☐☐
080-32
Mains voltage
V
3 400 ... 480 AC
3 400 ... 480 AC
Rated power
kW
0.47
1.36
Output current
400 V
A
1.0
2.8
480 V
A
0.8
2.3
Power factor
cos ϕ
0.99
0.99
Efficiency
Partial load η75 %
%
65.0
73.0
Full load η100 %
%
66.0
74.0
Moment of inertia
Without brake
kgcm
2
3.700
28.000
With brake
kgcm
2
3.715
28.061
Technical data
Standards and operating conditions
EMC data