6
Commissioning
6.4
Setting the IP configuration
40
Lenze · E94AYCER communication module (PROFINET®) · Communication Manual · DMS 11.0 EN · 04/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.4.2
Setting via codes in the »Engineer«
In the »Engineer« under the
Settings
tab you can set the IP parameters manually via code.
The IP parameters are written to codes
/
(IP address),
/
(subnet
mask) and
/
(gateway address).
How to activate changed settings in the »Engineer«:
1. Execute the device command
C00002 = "11: Save start parameters"
.
2. Carry out a "Reset node" of the node, or switch the voltage supply of the communication
module off and then on again
Note!
• The IP address must only be allocated manually in the »Engineer« if the PROFINET
network is not operated on the IO controller yet (IP address has not been allocated by
the IO controller yet).
• While setting the IP parameters in the »Engineer«, PROFINET communication with the
IO controller must not take place at the same time.
• The currently used parameter values are shown in codes
/
(IP
address),
/
(gateway address).