• Interface module for the PROFINET IO communication system, for attaching to the expansion
slots of Servo Drives 9400
• The communication module can either be supplied internally by the standard device or
externally by a separate voltage source.
• Support of the I&M0...4 functionality for the identification of the standard device
• Automatic detection of the baud rate 100 Mbps
• A line topology is enabled by the integrated 2-port switch.
• Support of the LLDP (Link Layer Discovery Protocol) for the topology recognition
• Support of the SNMP (Simple Network Management Protocol) for diagnostic purposes
• Support of the MRP (Media Redundancy Protocol)
from SW version 2.10
The Servo Drive 9400 can be integrated as client node into a ring topology.
• Support of the "Shared Device" function
from SW version 2.10
• Transfer of safe information via the PROFIsafe protocol if the SM301 safety module (E94AYAE)
is used simultaneously
From SW version 3.00
onwards, the SM302 safety module (E94AYAF) can also be used.
• Up to 32 process data words (64 bytes) per direction can be exchanged.
• Access to all Lenze parameters
• An online connection via PROFINET can be established using the Lenze »Engineer«.
From
SW version 2.10
onwards, up to 3 connections are supported at the same time.
Note:
It must be ensured that file services accessing a file (e.g. load parameter set) are always
only executed via one engineering tool. Otherwise file access errors will occur.