Electrical installation
24
Lenze · E94AYCER communication module (PROFINET®) · Communication Manual · DMS 11.0 EN · 04/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.2
Electrical installation
5.2.1
Wiring according to EMC guidelines
In typical systems, standard shielding is sufficient for Ethernet cables.
However, in environments with a very high level of interference, EMC resistance can be improved
by additionally earthing the cable shield on both sides.
For this observe the following notes:
1. The distance between the additional earthing and the Ethernet plug depends on the module
slot and is as follows:
• approx. 10 cm for the upper slot (MXI1)
• approx. 20 cm for the lower slot (MXI2)
2. Measure the appropriate distance along the cable and, starting from this point, remove 2 cm of
the cable's plastic sheath.
3. Connect the cable shield to the shield sheet of the Servo Drive 9400.
[5-3]
Wiring according to EMC guidelines
Documentation for the standard device, control system, system/machine
Observe the notes and wiring instructions contained in this documentation.
E94YCXX008
A
Connection to the shield sheet of the Servo
Drive 9400
B
Outgoing PROFINET cable at X242
C
Incoming PROFINET cable at X241
D
Communication module in slot MXI1 of the
Servo Drive 9400