After the UPS is repaired, start the UPS following the startup procedure, then turn

manual bypass switch to position AUTO (A).  The UPS will switch back to normal operation

mode within 20 seconds.

For NBP-0811, NBP-1011 which have manual bypass circuit breaker (option), when

UPS is malfunction, please turn on manual bypass circuit breaker.  The UPS changes to

operate in bypass mode.  INVERTER LED  is  off  while MAINTENANCE  BYPASS LED and

alarm sound is on.  All loads which connected to UPS OUTPUT are switched to connect to

utility power for temporary use.  Then press POWER switch at the front to shutdown the

UPS, turn off  INPUT circuit breaker and contact us or nearest service center.

After the UPS  is repaired, start the UPS following the startup procedure, then turn off manual

bypass circuit breaker.  The UPS will switch back to normal operation mode within 20 seconds.

5.6 LAN Interface (I/F) or RS232-PC

To communicate with computer or network, user is allowed to connect the

signal from DB9 connector to your computer to get the status as below,

5.6.1 POWER FAILURE shows utility power fails.

5.6.2 LOW BATTERY shows batteries are going to run out of power.

5.6.3 SHUTDOWN UPS When utility power fails and UPS is going to run out of

battery, computers and network are automatically save files or data.  Then send

signal to UPS to shutdown the whole system.

- 17 -

5.3.3 When loads connected to UPS consume power more than 125% of the UPS

capacity, OVERLOAD indicator will be it. To protect the UPS from damages,

LEONICS designed Automatic Transfer Switch system to bypass the system.

At that time, the power supplies to loads is direct from utility line.  This

situation may happen when loads draw very high current such as when user

turns on computers.  When the loads consume power less than 125% for 10

seconds, UPS switches back to normal operation mode.

5.3.4 If you connect loads to UPS more than 100% (OVERLOAD indicator is lit ),

we recommend you to unplug some of them until %load is less than 100% to

let loads get high quality power from UPS and backup power from battery

Note: LEONICS suggests that for highest reliability and safety that you should

connect loads at no more than  75 % of rated UPS power. This allow for loads

that change  power level during use and provides for some reserve backup power

for some  loads.

5.4 Using UPS when power fails

5.4.1 When power line fails, UPS still supplies power which comes from backup

batteries to load for 15-90 minutes.  The duration that it can supply depends

on %load and battery level. When battery power is weak (about 2 minutes

before UPS fully shuts down),  LOW BATT.  indicator is blinking and alarm sounds

To  mute the alarm, press FUNC. button.  When utility power returns to

normal status and UPS still has backup power left, UPS automatically switches

back to normal operation and charges battery at the same time.

5.4.2 When UPS is supplying backup power and does not have any loads connected,

UPS will shut down in 10 seconds to save battery backup power. (Set Noload

shutdown switch is on position).

5.5 Using UPS when UPS is malfunction

For NB 2K25, NBP 3K25, NBP 5K25 and NBP 6K25 which have manual bypass switch

(option), when UPS is malfunction, please turn the manual bypass switch at the back of

the UPS from position AUTO (A) to position BYPASS (B).  The UPS changes to operate in

bypass mode.  INVERTER LED is off while MAINTENANCE BYPASS LED and alarm sound is

on.  All loads which connected to UPS OUTPUT are switched to connect to utility power

for temporary use.  Then press POWER switch at the front to shutdown the UPS, turn off

INPUT circuit breaker and contact us or nearest service center.

Summary of Contents for NB 1K25

Page 1: ...NBP series NB series TRUE ON LINE DOUBLE CONVERSION UPS LEN MAN UPS 068 Rev 3 00 2008 www leonics com e mail global_business leonics com U S E R S G U I D E ...

Page 2: ...CONTENT SAFETY INSTRUCTIONS 1 INTRODUCTION 3 FRONT AND REAR PANEL 6 INSTALLATION 14 OPERATION 16 TROUBLESHOOTING 19 MAINTENANCE 20 ...

Page 3: ... plugging and unplugging the load in order to avoid electric shock from touching two surfaces with different potential 1 1 8 It is recommended to connect the UPS to a three wire AC source two poles plus ground which connects to a protected circuit such as employs a fuse or automatic circuit breaker 1 2 CAUTION Safety guide for installation and operation 1 2 1 Install the UPS in dry location with g...

Page 4: ... to avoid electric shock 1 3 5 Replace batteries with the same type and rating and follow the proper battery replacement procedure Vocabulary Load Any equipment which is plugged into the UPS and gets power from the UPS such as a computer printer fax machine or modem UPS NB Series and NBP series UPS VA The unit of UPS power rating showing its capacity 2 2 1 When utility power and loads are normal A...

Page 5: ...on and turn off the UPS 3 1 2 FUNC button The button to mute alarm sound or turn on the LCD s back light The back light will turn off automatically in 10 seconds after release this button 3 1 3 LINE indicator The Indicates when utility line normally 3 1 4 RECTIFIER indicator The indicator is displayed when utility line normally It supplies power to the UPS in rectifier section and supplies power t...

Page 6: ...al port to connect the LAN cable to computer network to monitor electrical and UPS status via SNMP HTTP Read more details in Net Agent manual 3 2 14 BATTERY TERMINAL for NBP0811 and NBP1011 The teminal for connecting to extension battery unit 3 1 13 LCD DISPLAY The screen to displays Input voltage Vin Output voltage Vout Battery Level B and Load level LD as shown in the picture below Note The valu...

Page 7: ...reaker OPTION Thecomponenttoswitchthepower source of loads to utility power when maintenance 3 1 18 SNMP AGENT OPTION The additional port to connect the LAN cable to computer network to monitor electrical and UPS status via SNMP HTTP Read more details in Net Agent manual 3 1 19 NO LOAD SHUT DOWN SWITCH The switch to enable automatic shutdown when there is no load and power fails No load means the ...

Page 8: ... 11 3 2 6 3 2 1 3 2 12 3 2 9 3 2 8 3 2 7 3 2 13 3 2 10 3 2 11 12 ...

Page 9: ...loads 3 2 11 GROUND The terminal for connecting to ground system 3 2 12 MAINTENANCE BYPASS SWITCH option Turn this switch to position B when UPS is under maintenance 14 INSTALLATION Model Input cable mm2 Output cable mm2 Earth cable mm2 Battery cable mm2 NB2K25 2 5 4 1 5 2 5 2 5 4 NBP 3K25 4 2 5 2 5 4 NBP 5K25 6 4 4 NBP 6K25 6 6 6 NBP 0811 10 6 10 6 6 NBP 1011 16 16 10 6 10 4 1 Connect the RS 232 ...

Page 10: ...rn on INPUT circuit breaker 5 1 2 2 Turn on POWER button and wait until INVERTER indicator is lit 5 1 2 3 Turn on BATTERY circuit breaker 5 1 3 Model NBP 0811 and NBP 1011 5 1 3 1 Turn on INPUT circuit breaker 5 1 3 2 Turn on POWER button and wait until INVERTER indicator is lit 5 1 3 3 Turn on BATTERY circuit breaker 5 1 3 4 Turn on OUTPUT circuit breaker Note When the UPS is out of order turn on...

Page 11: ...ch as when user turns on computers When the loads consume power less than 125 for 10 seconds UPS switches back to normal operation mode 5 3 4 If you connect loads to UPS more than 100 OVERLOAD indicator is lit we recommend you to unplug some of them until load is less than 100 to let loads get high quality power from UPS and backup power from battery Note LEONICS suggests that for highest reliabil...

Page 12: ... UPS is turned on UPS does not supply backup power when power fails No indicator displays at the panel when the UPS is turned on UPS does not supply backup power when power fails MODEL PROBLEM SOLUTION 20 6 2 How to turn on INPUT circuit breaker for NB2K25 NBP 3K25 NBP 5K25 NBP 6K25 NBP 0811 and NBP 1011 6 2 1 Turn off the UPS by pressing the POWER button at the front panel 6 2 2 Turn on the INPUT...

Page 13: ...n user wants to use the UPS plug the INPUT CABLE to wall outlet utility line Turn on POWER button and wait until the ventilation fan blows Then turn on BATTERY circuit breaker 7 4 2 Model NB 2K25 NBP 3K25 NBP 5K25 and NBP 6K25 7 4 2 1 Turn off the UPS by pressing the POWER button at the front panel 7 4 2 2 Turn off the BATTERY circuit breaker 7 4 2 3 Turn off the INPUT circuit breaker 7 4 2 4 When...

Reviews: