LEN.MAN.UPS.169 Rev.3.00/2013

SPECIFICATION

SAFETY INSTRUCTIONS

 

Please read carefully and follow this UPS guide and keep this user's guide 

for reference in order to use the UPS properly and safety. This user's guide 
contains instructions for installation, preservation, operation and 
specification. 
 

For product safety, please check this product annually by our service 

qualified personnel or if there are any symptoms of problems which are not 
mentioned in this guide or an queries, please contact your local distributors 
or service center.

Warning

 

 

Risk of electric shock, DO NOT remove cover. No user serviceable  

 

 

 

part inside, please refer servicing to qualified service personnel.

1.  Electrical Safety

  1.1  Do not work alone under hazardous condition.
  1.2  Contact with live conductors will cause burns and dangerous electric
   shock.
  1.3  Periodically check your cables, outlets and power source to make sure   
   

that they are in good condition.

  1.4  To reduce the risk of electric shock if you cannot find the electrical  

 

   

ground (       ) of building, unplug UPS from AC source before plug in    

   

your loads at the rear side of the UPS. Then, plug in the UPS to AC  

 

   source.
  1.5  Do not touch any metal parts or any electrical connections when UPS is  
   operating.
  1.6  Use ONLY one hand when plugging and unplugging the load in order   
   

to avoid electric shock from touching surfaces with different potential.

  1.7  It is recommended to connect UPS to a three wire AC source (two live    
   

wires and ground) which connect to a protected circuit such as fuse or  

   circuit 

breaker.

2.  CAUTION! Safety instructions for installation and operation

  2.1  Before installing or using this UPS, read all instructions, caution making  
   

on UPS and all connected loads, and all sections of this user's guide.

  2.2  Install UPS in a temperature and humidity controlled indoor area with   
   

sufficient ventilation and away from dust, chemical particles or  

   

flammable substances. Avoid installing UPS in areas near radio  

 

   

 transmission station, heat dissipation equipment or direct sunlight.

  2.3  UPS has ventilation grills on the sides. Ensure that sufficient ventilation  
   

is provided, do not block the ventilation grills. The distance of   

 

   

minimum 30 cm between wall and unit is necessary.

  2.4  Use insulated tools to reduce the risk of electric shock.
  2.5  Remove all ornaments or other metal objects such as rings, necklaces,  
   

 bracelets and watches before installing.

  2.6  Before connecting the communication interface signal cable to  

 

   

computer, turn off UPS and disconnect it from AC source.

  2.7  Turn on UPS before turning on connected loads to prevent surge from  
  

 

the 

loads.

  2.8   Do not connect AC source input to UPS output. This may cause UPS    
  

damage.

  2.9  When heavy rain, avoid using electronic equipments including UPS to  
   

 prevent them from lightning.

  2.10  Do not clean UPS with benzene, thinner or any solvent, use only soft    
   

cloth to clean UPS after it has been turned off.

  2.11  Do not use the UPS with life recovery instruments. The failure of UPS    
   

may cause life recovery instruments failure or effect to their    

 

   

performance or the safety system of those instruments.

3.  Warning! Battery Safety

  3.1   Although UPS is disconnected to any power source, UPS outlets may    
   

be energized because there is a battery inside the UPS.

  3.2   The UPS has hazardous voltage inside, do not dissemble any parts of    
   

UPS. Battery replacement must be done by Leonics qualified    

 

  

technicians 

only.

  3.3   The batteries inside UPS can be recycled. It contains lead which is  

 

   

harmful to your health and environment. If it cannot be disposed  

 

   

of properly, please return it to local distributors or Leonics Service  

 

  

Center. 

  3.4   Do not dispose batteries with fire, they will be exploded.
  3.5   Do not disassemble batteries. They contain poisonous electrolyte  

 

   

which is harmful to your skin and eyes.

  3.6   Replace batteries with the same type and rating.

U S E R ' S   G U I D E

 

www.leonics.com

 

MICROPROCESSOR CONTROL AND

LINE INTERACTIVE UPS WITH STABILIZER

(1)

 Pentium 4, 1.8 GHz chip computer with monitor 15", 

(2)

 Bubble jet or dot matrix printer, 

(3)

 Easy-Mon V Software compatible with

   Windows 98/2000/2003/XP/Vista X/2008/Windows 7, Redhat Linux 8/Redhat enterprise AS3/Suse Linux 10/Ubuntu 6.10/Fedora 5,

   Solaris 10, Mac OS X/10.3/10.4/10.5.

Continuous product development is our commitment. In that manner, the above specifications may be changed without prior notice.

UPS system

Control system

Stabilizer function

The number of PC

(1)

Input voltage

Frequency

Voltage battery mode

Voltage AC mode

Over voltage

Under voltage

Transfer time

Overload (AC mode)

Overload (DC mode)

Overload shortcircuit

Surge energy dissipation

Power dissipation

Acoustic noise

Type

Capacity

Backup time

Continuous recharging time

Number of backup outlet

Number of surge protection outlet

(not backup)

AC/DC start

Communication interface

Monitoring and Management

Software

Surge protection for telephone line

Surge protection for LAN line

Surge protection for laser printer

LCD display

Battery mode

Low battery

Overload

Battery replacement

Fault

Temperature

Humidity

W x H x D (mm.)

Approximate in kg.

MODEL

POWER RATING

SYSTEM

LOAD APPLICATION

INPUT

OUTPUT

PROTECTION

BATTERY

OUTPUT OUTLET

FEATURE

INDICATOR

AUDIBLE ALARM

(BUZZER)

ENVIRONMENT

DIMENSION

WEIGHT

 

OA-650 OA-750 OA-1100 OA-1600

  650 VA/390W    750VA/450W  1100VA / 605W  1600VA / 960W

 

Line interactive UPS with Stabilizer

 

Microprocessor 8 bit

 

Buck / Boost

 

1 set+printer

(2)

  2 sets+printer

(2)

 3 sets+printer

(2) 

4 sets+printer

(2)

 

220 Vac ± 20%

 

50 Hz ± 10%

 220 

Vac

 

220 Vac ± 10%

 

Mains to UPS backup 220 Vac + 20%

 

Mains to UPS backup 220 Vac - 20%

 

2 - 6 msec. typical, 10 msec. maximum

 yes

 yes

 software 

detection

 

125 Joules / 2 ms. x 3

 

1,000,000 W within 100 microsec.

 

Less than 40 dBA at 1 metre

 

Sealed lead acid (maintenance free)

  1 x 12 V 7 Ah  1 x 12 V High Rate  2 x 12 V 7 Ah  2 x 12 V High Rate

 

15 - 40 min. (depending on connected load)

 

4 to 6 hours (90% after full discharged)

 3 

5 6

 1 

1 2

 

 yes

 USB 

port

 

Easy-Mon V software

(3)

 yes

 no 

option

 yes

  AC mode, Battery mode, Load level, Battery level, Input

  voltage, Output voltage, Overload, Fault, and Low battery

 

Audible beep every 10 seconds

 

Audible beep every second

 

Audible beep every 0.5 seconds

 

Audible beep every 2 seconds

 

(Battery test function on Easy-Mon V software)

 Continuous 

beep

 

0 - 40˚C

 

0 - 90% (non-condensing)

 100 x142 x 287  100 x 142 x328  146 x 160 x 350  146 x 205 x 397

 4.45 

4.81 

8.0 

11.5