background image

SAFETY INSTRUCTIONS

Please read carefully and follow this OA EXTRA series UPS guide.

Important :

Please keep this user's guide for reference in order to use the UPS properly
and safety. This user's guide contains instructions for installation, operation
and specifications.

For product safety, please check this product annually by our service qualified per-

sonnel or if there are any symptoms of problems which are not mentioned in this guide or
an queries, please contact your LEONICS local distributors,LEONICS Service Center, send
e-mail to support@leonics.com or visit www.leonics.com.

Caution

Risk of electric shock, DO NOT remove cover. No user serviceable part
inside,  please refer servicing to qualified service personnel.

1.1 Electrical Safety

1.1.1 Do not work alone where there are electrically hazardous conditions.
1.1.2 Contact with live conductors will cause burns and dangerous electric shock.
1.1.3 Only qualified electricians allow to install and wiring this unit and the system.
1.1.4 Periodically check your cable, terminal and power source to make sure that

they are in good condition.

1.1.5 To reduce risk from electric shock if you can not find the electrical ground

 ) of the building, unplug the UPS from the AC source before plug in your

load at the rear side of the UPS. Then, plug in the UPS to AC source.

1.1.6 Do not touch any metal parts or any electrical connection when UPS is operating.
1.1.7 Use ONLY one hand when plugging and unpluging the load in order to avoid

electric shock from touching two surfaces with different potential.

1.1.8 It is recommended to connect the UPS to a three wire AC source (two live wires

and ground) which connects to a protected circuit such as employs a fuse or
circuit breaker.

1.2 CAUTION ! Safety guide for installation and operation

1.2.1 Before installing or using this unit, read all instructions, caution markings on

the UPS and all connected load,  and all sections of this user guide.

1.2.2 Install this unit in a temperature and humidity controlled indoor area with

adequate air flow and away from chemical particles or flammable substances .
Avoid installing the unit near radio transmission station, heat dissipation equip-
ment and direct sunlight.

1.2.3 This unit has ventilation grills. Ensure that sufficient ventilation is provided.

DO NOT block the ventilation grills.

1.2.4 Use insulated tools to reduce your risk of electric shock.
1.2.5 Remove all jewelry or other metal objects such as rings, necklace, bracelets

and watches when installing this product.

1.2.6 Properly wiring the cables as shown in the wiring diagram.
1.2.7 Before connecting the communication interface signal cable, Turn off the UPS

by pressing the front panel button until the Utility Line OK/Fail (          ) and
Overload Alarm (          ) lamps are lit at the same time and the alarm sounds
once. Then, release the button.

1.2.8 Turn on the UPS before turn on the load to prevent surge from the loads.
1.2.9 DO NOT connect utility power to the UPS OUTPUT.  This may cause the UPS

damaged.

1.2.10When heavy rain, avoid using electronic equipments including UPS to prevent

it from lightning.

1.2.11Use soft cloth to clean the UPS when it is turned OFF.  DO NOT clean it with

solvent.

1.2.12DO NOT use the UPS with life recovery instruments.  The failure of UPS may

cause life recovery instruments failure or effect to their performance or effect
to the safety system of those instruments.

1.3 Warning ! Battery Safety

1.3.1 Although the UPS is not connected to any power source, its outlets may be

energized because it has a battery inside.

1.3.2 The UPS has hazardous voltages inside, do not disassemble any parts of UPS

except for the battery. Users are allowed to replace battery by turning off power
switch at the rear side of the UPS, then unplug the AC input cable. Users are not
allowed to repair, recondition or disassemble the UPS. This must be done by
Leonics qualified technicians only.

This product contains sealed lead acid battery and must be recycled

properly. For recycling please return it to a LEONICS local distributor or
LEONICS Service Center or contact your local recycling center for proper
disposal information.

1.3.3 Do not dispose of batteries in a fire. They may be exploded.
1.3.4 Do not disassemble batteries. They contains poisonous electrolyte which is

harmful to your skin and eyes.

1.3.5 Replace batteries with the same type and rating and follow the proper battery

replacement procedure.

1.3.6 When replacing a battery, use tools with insulated handles and remove any

watch, rings or other metal objects that you wear in order to avoid electric shock.

1.3.7 If user has to keep the UPS or does not use if for long time, recharge the battery

every 3 months in order to preserve the battery.  To recharge the battery,
connect it to the AC utility and turn on the UPS for 8 hours.

SPECIFICATION

*PC = Pentium 4 , 1.8GHz  with 15” monitor respectively., **Printer = Bubble jet or Dot matrix printer.
Continuous product development is our commitment. In that manner, the above specifications may be changed without prior notice.

MODEL

OA EXTRA 525 OA EXTRA 750 OA EXTRA 1000 OA EXTRA 1500

CAPACITY

Power factor = 0.6

525 VA (315W)

750 VA (450W)

1000 VA (600W)

1500 VA (900 W)

SYSTEM

UPS system

Digital Line Interactive UPS

Control system

Microprocessor 8 bit

Stabilizer function

Buck / Boost

LOAD

The number of PC*

1 set + printer** 2 sets + printer**

3 sets + printer**

4 set + printer**

APPLICATION

INPUT

Input Voltage

220 Vac ± 25% (230 Vac option)

Nominal Input (single phase)

220 Vac (230Vac option)

Frequency

50Hz ± 6% (60Hz ± 6%) (auto sensing) (50Hz ± 10% option)

OUTPUT

Voltage  stabilizer mode (sine wave)

220 Vac ± 10% (230 Vac option)

Voltage backup  mode for 1 PC

220 Vac ± 5% (230 Vac option)

(modify sine wave)

Frequency (backup mode)

50Hz ± 0.1% (60Hz ± 0.1%) (auto sensing)

PROTECTION

Transfer time

5 ms. (in-phase transfer)

Output short circuit

Auto cut - off with audio & visual alarm

Overload protection

Fuse protection

Circuit breaker

Surge energy dissipation

STD. UL1449 : 160 Joules (IC = 6500A)

Power dissipation

1,600,000 W within 100 microsec.

Acoustic noise

Less than 40 dBA at 1 metre

BATTERY

Type

Sealed lead acid (maintenance free)

Capacity

12 V 7 Ah

12 V High Rate

2 x 12 V 7 Ah

2 x 12 V High Rate

(12 V High Rate option)

Backup  time

15 - 40 min. (depend on load)

Continuous recharging time to 80%

3 - 8 hours

OUTPUT OUTLET

Number of backup outlet

3

6

Number of surge protection outlet

1

1

FEATURE

Power Watcher

yes

Noload shutdown option switch

yes

Backup test switch

yes

DC start

yes

Communication interface

Level communication (DB-9)

Easy-Mon software

UPS status, Backup time remaining, Schedule shutdown computer and UPS

Restart voltage checking system

yes

Surge protection for telephone line

yes

Surge protection for LAN line

option

Surge protection for laser printer

yes

Operating with generator

yes

User replaceable battery

yes

ENVIRONMENT

Temperature

0 - 45°C

Humidity

0 - 95% (non - condensing)

PHYSICAL

W x H x D (cm.)

10 x 16.5 x 30

10 x 16.5 x 30

12.5 x 21 x 36

12.5 x 21x 36

DIMENSIONS

WEIGHT

Approximate in kg.

8

8.5

14

17

CONFORMANCE

Design regulation

EN 50091-2, EN 50022 (B), EN 61000-4-2, (4), (6), IP 21

Reviews: