background image

- 28 -

Symptoms

Possible Causes

Solutions

UPS operates normally

but the lamp no.3 is blink

or LCD display show over

load sign on the top bar of

load level display

UPS operates normally

but sounds a short beep

periodically or UPS switches

to backup power for a short

period and returns to

normal operating status.

When a black out occurs,

UPS supplies backup

power but it is still

supplying when the AC

source recovers.

4. If you follow steps 1- 3

and the  symptoms still

exist, the fuse might be

blown.

Loads which are connected

to Power Watcher ( UPS

output ) are exceed the

UPS rated capacity.

A power sag occurred in

too short a period for the

user to sense. But UPS can

detect that abnormal

condition.

The returned AC source's

voltage is too low for

ULTRA Series UPS to run in

normal operating mode.

Check fuse holder (for

ULTRA Series UPS 650VA or

smaller).  If fuse is blown,

replace with the spare fuse.

If the UPS does not

operate, please send it to

a LEONICS Service Center.

Reduce  loads to 75%.

(please keep the remain

25% available for

instantaneous power

consumption of the load

when it first starts. )

Do nothing, normal

operation.

- Turn off  loads and wait

until the AC source

returns to normal. Then

turn  on loads again.

or

- Use backup power from

UPS until  battery low

alarm alerts, then turn

off  loads and the UPS.

Wait until the AC source

returns to normal, then

- 29 -

Symptoms

Possible Causes

Solutions

UPS operates normally

but sometimes the

overload alarm alerts.

UPS does not supply

backup power during a

black out and the lamp

no. 8 to no.11 are all lit

(LED display only).

1. Loads are consuming

more power  than usual

at that time. Often this

is caused by a printer

when it is printing.

2. Overload may come

from a laser printer or

another load that

connected to the UPS

output outlet.

turn on loads and the

UPS again.

or

- If AC source is normal,

but the UPS still has the

same symptom, see

solution of the first

symptom In this list.

Reduce the loads.

Unplug laser printer from

the UPS output outlet and

plug into the socket for

laser printer (protected

from surge only).

1. Unplug all loads from

UPS. Shutdown the UPS

and restart again.

2. If the UPS still has the

same symptom, shut-

down the UPS and

follow battery replace-

ment  instructions.

Disconnect the red wire

from battery connector

5 minutes later, then

shutdown UPS and restart.

Summary of Contents for Ulta Series

Page 1: ......

Page 2: ...nd quick reference for our service please fill the requested information in the blanks below UPS Model __________________________________ Serial Number __________________________________ Purchased dat...

Page 3: ...including UPS to prevent it from lightning 1 2 11Use soft cloth to clean the UPS when it is turned OFF DO NOT clean it with solvent 1 2 12DO NOT use the UPS with life recovery instruments The failure...

Page 4: ...ced Load Outlet Management ALOM which the user can program to turn off a low priority outlet when there is a low battery or overload condition for 1050VA or higher only For the UPS with LED display an...

Page 5: ...e Power Watcher provides information about load conditions whether or not you are overloading your ULTRA Series UPS PowerWatcher is continuously monitoring in real time both for the stabilizer and inv...

Page 6: ...et the intelligent output channel to cut off power to low priority loads when the UPS is overloaded over temperature or has a low battery available on 1050 VA or higher model only 8 Hot Swappable Batt...

Page 7: ...y power status Lit UPS is operating under its normal mode Blink UPS is operating in the backup mode Note 1 For the UPS with inverter temperature sensor option It will be blink fastly when the temperat...

Page 8: ...inks only at a time Please refer to section 6 3 The meaning of LCD display 3 1 7 Battery Level Shows the battery voltage from low to high level 3 1 7 1 For the UPS with LED display Lamp no 4 11 green...

Page 9: ...3 2 5 2 Intelligent Channel A supplemental outlets that the user can manage and control by Easy Mon X Software See item 12 2 The Intelligent Channel can be set to permanently turn on or can be set to...

Page 10: ...h enable disable ULTRA Series UPS 650VA or smaller ULTRA Series UPS 1050VA or higher Set the dip switch SW1 to ON as shown if you want the UPS to shutdown automatically in backup mode when the load is...

Page 11: ...wer cord to the electrical outlet Press the multi function switch for 0 5 second then release All indicator lights will blink after that UPS will start up the self test See details in section 5 3 1 Wh...

Page 12: ...de provided on the accompanying CD ROM 5 3 4 Auto test every 2 weeks If there is no manual or scheduled self test during the past 2 weeks the UPS will do a self test automatically You can also set the...

Page 13: ...e lit when load are between 51 to 75 Lamp no 4 5 6 and 7 are lit when loads are between 76 to100 Lamp no 4 5 and 6 are lit and lamp no 7 is blink when loads are over 100 and you should reduce the load...

Page 14: ...The lamp no 9 is lit when self test is cancelled because of battery power is too low The lamp no 11 is lit when it need to replace the battery 24 25 6 3 The meaning of LCD display 6 3 1 Input Voltage...

Page 15: ...en a stabilizer fault The second indicator is lit when a charger fault 27 The third indicator is lit when software failure The forth indicator is lit when CPU error The fifth indicator is lit when an...

Page 16: ...the load when it first starts Do nothing normal operation Turn off loads and wait until the AC source returns to normal Then turn on loads again or Usebackuppowerfrom UPS until battery low alarm alert...

Page 17: ...or 31 When the UPS warns you to replace the battery see details in item 6 2 3 2 and 6 3 4 2 Warning You can replace UPS s battery while it is operating But for your safety we recommends that you turn...

Page 18: ...reconnect each wires connection to each battery same as before Put the battery strip back in its position 9 6 Re screw the battery strip with the case 9 7 Replace and screw the front panel in place a...

Page 19: ...Driver to read the instructions for installing USB driver 12 5 Follow the instruction on screen to install UPS driver 12 6 When installation is completed restart computer 12 7 Install Easy Mon X Packa...

Reviews: