- 14 -

3.2.1 Surge protection for telephone line / LAN line (option): A port for fax / modem

line  surge protection. Its function is to protect load against voltage spikes

coming from the telephone or LAN line (option).

3.2.2 No Load Shutdown Switch: Allows you to select whether the UPS will shutdown

itself when power line fail if there is no load or not (no load are defined as all

loads that connected to the UPS are less than 8 percent of UPS capacity).

3.2.3 USB Port or RS-232 port (option): The communication port for connecting the

UPS to PC.  The signal from the UPS will send information to the PC through this

port via USB cable or RS-232 cable (option) and display data on Easy-Mon X

Monitoring Software.

3.2.4 Full time surge protection output for laser printer: The outlet that connects

surge protection circuit. This socket is for Laser Printer or other high power

consumption devices such as scanner.  There is no backup power from this

outlet.

3.2.5 UPS output :  Loads supplied from these outlets are full time monitored under

Power Watcher.  They are provided for the loads that the user wants to protect

and provide a back up power supply when there is a power failure.  Loads may

be added until Power Watcher warns of an overload.  (LEONICS suggest to

connect load at no more than 75 % of UPS rated power for safety and enough

backup power for those loads that need irregular power.) For 1050 VA or higher

model, the UPS output has two channels as follows.

3.2.5.1 Main Channel: The main outets that is always connected to the UPS

backup system.  It is provided for high priority electrical equipments

such as a computer or server.

3.2.5.2 Intelligent Channel:  A supplemental outlets that the user can manage

and control by Easy-Mon X Software (See item 12.2). The Intelligent

Channel can be set to permanently turn on or can be set to perform in

intelligent mode to :

1. Turn on with a delay of 0 - 4,000 seconds after the Main Channel

turn on.

2. On commercial power :

2.1 Turn off when there is UPS overload.

2.2 Automatic re-supply after an overload has been removed.

- 15 -

3. On Battery Operation :

3.1 Turn off when UPS gets over temperature.

3.2 Turn off when battery is low.

3.3 Turn off when there Is UPS overload.

Note: 1.

Intelligent Channel is set to permanently 'ON' from the factory.

2.

If set the Intelligent Channel to On battery operation mode and

disabled, the UPS will re-supply automatically when the utility

power returns to normal.

3.

Loads which are connected to the Intelligent Channel should

be low prioirty such as a printer or scanner.

3.2.6 AC input:  The power socket for plug in the input power cord.  In Ultra Series

UPS 650 VA or smaller, it is the power socket with buit-in fuse holder and spare

fuse holder socket.

3.2.7 Fault wiring:  A indicator light shows the fault wiring of the utiliy line which

connects to the UPS. The fault wiring can be either the wiring of line or neutral

are crossed or no electric ground. If this indicator light is extinguished, it means

the wiring is correct.

3.2.8 Battery extension port (option):  The port for connecting with an extension

battery unit to increase the duration of UPS backup time.

3.2.9 Dip switch:  The switch for setting the no load shutdown system. The switch

no.1 use for enable/disable no load shutdown system.

Note:  SW 2 -  SW 4  are not available at the present.

3.2.10  Magnetic breaker: A circuit breaker that protects the UPS from overload or

 short circuit current (available on 1050 VA or higher model).

Summary of Contents for Ulta Series

Page 1: ......

Page 2: ...nd quick reference for our service please fill the requested information in the blanks below UPS Model __________________________________ Serial Number __________________________________ Purchased dat...

Page 3: ...including UPS to prevent it from lightning 1 2 11Use soft cloth to clean the UPS when it is turned OFF DO NOT clean it with solvent 1 2 12DO NOT use the UPS with life recovery instruments The failure...

Page 4: ...ced Load Outlet Management ALOM which the user can program to turn off a low priority outlet when there is a low battery or overload condition for 1050VA or higher only For the UPS with LED display an...

Page 5: ...e Power Watcher provides information about load conditions whether or not you are overloading your ULTRA Series UPS PowerWatcher is continuously monitoring in real time both for the stabilizer and inv...

Page 6: ...et the intelligent output channel to cut off power to low priority loads when the UPS is overloaded over temperature or has a low battery available on 1050 VA or higher model only 8 Hot Swappable Batt...

Page 7: ...y power status Lit UPS is operating under its normal mode Blink UPS is operating in the backup mode Note 1 For the UPS with inverter temperature sensor option It will be blink fastly when the temperat...

Page 8: ...inks only at a time Please refer to section 6 3 The meaning of LCD display 3 1 7 Battery Level Shows the battery voltage from low to high level 3 1 7 1 For the UPS with LED display Lamp no 4 11 green...

Page 9: ...3 2 5 2 Intelligent Channel A supplemental outlets that the user can manage and control by Easy Mon X Software See item 12 2 The Intelligent Channel can be set to permanently turn on or can be set to...

Page 10: ...h enable disable ULTRA Series UPS 650VA or smaller ULTRA Series UPS 1050VA or higher Set the dip switch SW1 to ON as shown if you want the UPS to shutdown automatically in backup mode when the load is...

Page 11: ...wer cord to the electrical outlet Press the multi function switch for 0 5 second then release All indicator lights will blink after that UPS will start up the self test See details in section 5 3 1 Wh...

Page 12: ...de provided on the accompanying CD ROM 5 3 4 Auto test every 2 weeks If there is no manual or scheduled self test during the past 2 weeks the UPS will do a self test automatically You can also set the...

Page 13: ...e lit when load are between 51 to 75 Lamp no 4 5 6 and 7 are lit when loads are between 76 to100 Lamp no 4 5 and 6 are lit and lamp no 7 is blink when loads are over 100 and you should reduce the load...

Page 14: ...The lamp no 9 is lit when self test is cancelled because of battery power is too low The lamp no 11 is lit when it need to replace the battery 24 25 6 3 The meaning of LCD display 6 3 1 Input Voltage...

Page 15: ...en a stabilizer fault The second indicator is lit when a charger fault 27 The third indicator is lit when software failure The forth indicator is lit when CPU error The fifth indicator is lit when an...

Page 16: ...the load when it first starts Do nothing normal operation Turn off loads and wait until the AC source returns to normal Then turn on loads again or Usebackuppowerfrom UPS until battery low alarm alert...

Page 17: ...or 31 When the UPS warns you to replace the battery see details in item 6 2 3 2 and 6 3 4 2 Warning You can replace UPS s battery while it is operating But for your safety we recommends that you turn...

Page 18: ...reconnect each wires connection to each battery same as before Put the battery strip back in its position 9 6 Re screw the battery strip with the case 9 7 Replace and screw the front panel in place a...

Page 19: ...Driver to read the instructions for installing USB driver 12 5 Follow the instruction on screen to install UPS driver 12 6 When installation is completed restart computer 12 7 Install Easy Mon X Packa...

Reviews: