10
CONNECTIONS
LEROY-SOMER
3.2 - Description of cables and protective devices
• These tables should never be used instead of current standards.
Note:
• The mains current value is a typical value which depends on the source impedance. The higher the impedance, the lower the
current.
• The fuses (UL approved) are intended for installations capable of delivering 5000 A maximum at 480 V.
P
(kVA
)
230 V single-phase power supply
230 V 3-phase power supply
400 V 3-phase power supply
CVA rating
I
gI fuses
Cable
s
CVA rating
I
gI fuses
Cable
s
CVA rating
I
gI fuses
Cable
s
or
or
or
circuit-
circuit-breaker
circuit-breaker
(A)
(A)
(mm
2
)
(A)
(A)
(mm
2
)
(A)
(A)
(mm
2
)
0.8
A 31M
7
16
2.5
A 31TL
5
8
1.5
A 31T
3
6
1.5
1.8
A 32M
14
25
2.5
A 32TL
7
16
2.5
A 32T
5
10
1.5
2.2
A 32TL
8
16
2.5
A 32T
6
10
2.5
4.7
A 32T
8
16
2.5
en
3.3 - Power terminal blocks
3.3.1 - Terminal block for power supply PB1
marked (L1, L2 and L3) or (L, N)
This terminal block is used to connect the 3-phase power
supply.
Screw terminal block: VMA 32
Tightening torque: 0,8 Nm
Max. cross-section: 2,5 mm
2
3.4 - Terminal blocks for options
3.4.1 - RS485 type serial link connector
This is an RJ 45 connector and is used to connect the PX LCD
console or a PC in order to use the VMA SOFT programming
software.
3.4.2 - P2 connector
This is used to connect the following option: local
potentiometer with integrated Run/Stop (BMA 31/32).
PB1 & PB2
RJ 45
P2
VMA 32 T
L1 L2 L3
VMA 32 M
L N