* The Enable/Reset terminal will not reset an O.Ld1 trip. Use the
Stop/Reset key.
** These trips cannot be reset for 10 seconds after they occur.
See the
Digidrive SK Advanced User Guide
for further information on possible causes of drive trips.
Table 8-1 DC bus voltages
Table 8-2 Alarm warnings/Display indications
FAIL
Problem when transferring
parameters (SmartStick) or when
changing the default settings.
The drive is running or enabled. Repeat the procedure with the
drive locked.
Trip code
Condition
Possible cause
Drive voltage rating
UV Trip
UV Reset
Braking level
OV trip
110V
175
215
*
390
415
200V
175
215
*
390
415
400V
330
425
*
780
830
* These are the absolute minimum DC voltages the drives can be supplied by.
NOTE
Display
Condition
Solution
OVL.d
I x t overload (I = current, t = time)
Reduce motor current (Load)
hot
Heatsink/IGBT temperature high
Reduce ambient temperature or reduce motor current
br.rS
Braking resistor overload
See
Digidrive SK Advanced User Guide
AC.Lt
Drive is in current limit
See
Digidrive SK Advanced User Guide
If no action is taken when an alarm warning appears, the drive will trip on the appropriate fault code.
NOTE