background image

DYNEO

®

Synchronous motors                               

with permanent magnets-drive

Commissioning

4474 en - 2011.04 / e

Summary of Contents for DYNEO

Page 1: ...DYNEO Synchronous motors with permanent magnets drive Commissioning 4474 en 2011 04 e...

Page 2: ...machines or installations In such cases it is essential that the user takes appropriate precautions against the motor restarting after an unscheduled stop The variable speed drive is designed to be ab...

Page 3: ...LSRPM MAGNETS MOTOR WITH FEEDBACK VIA HALL EFFECT SENSOR CONTROLLED BY A UNIDRIVE SP DRIVE 6 3 COMMISSIONING OF LSRPM MAGNETS MOTOR WITH FEEDBACK VIA ENCODER WITH COMMUTATION CHANNELS CONTROLLED BY A...

Page 4: ...on each pair U U V V The thermal sensor is connected in the motor terminal box 1 Use shielded cable on each pair U U V V 15 14 13 16 9 3 2 1 4 5 6 7 8 17 12 11 10 _ _ MD ENCODER 3 15V MD Encoder 5V T1...

Page 5: ...r rated voltage 00 10 Motor rated frequency Enter the motor parameters indicated on the motor nameplate 00 14 Type HALL EFFECT or incremental UVW depending of the sensor used 00 15 Drive encoder lines...

Page 6: ...t limiting 150 0 41 The SWITCHING FREQUENCY value must be set according to the following table 0 42 Number of poles calculation p 120f n 0 45 Motor thermal constant 89 5 22 Enable high speed ON Enter...

Page 7: ...ual ref 3655 Setting the control parameters for the motor brake managed by the drive Possible to uncouple the motor YES NO Using the information on the motor nameplate set the following parameters 3 2...

Page 8: ...and 11 of the drive control terminal block To modify sensor control see parameter 7 15 0 21 2 Connect the shielding 360 round the connector 3 Connect the shielding 360 round the shielding connection...

Page 9: ...lete the motor stops automatically The procedure can be interrupted at any time by sending a stop command pressing the stop button on the keypad or opening the disable circuit Regardless of the requir...

Page 10: ...erminal block ADI3 0V terminals and set 00 28 CTP 1 Enter the main parameters 00 06 MOTOR RATED CURRENT A 00 07 MOTOR RATED SPEED rpm 00 08 MOTOR RATED VOLTAGE V 00 10 MOTOR RATED FREQUENCY Hz 05 24 E...

Page 11: ...04 e LEROY SOMER 5 CONNECTIONS 5 1 Motors U1 L1 V1 L2 W1 L3 5 2 Hall effect sensor Frame size 160 Frame size 160 1 U 2 W 3 V 4 U 5 W 6 V 7 0V white 8 15V brown 9 shielding 10 11 PTC green yellow grey...

Page 12: ...3 14 15 16 17 Pins 1 to 3 are not connected The cable general shielding is connected to the connector casing 5 4 Forced ventilation Black W V CP2 C P 1 Z U Blue Brown Motor type Capacitors CP1 CP2 LS...

Page 13: ...474 en 2011 04 e LEROY SOMER 5 5 Brake Power supply Coil 400 VAC 230 VAC 180 VDC 180 VDC Wiring 2 1 Coil Power supply S O8 _ A 15 2 1 depending on power supply and coil depending on power supply and c...

Page 14: ...Commissioning DYNEO Synchronous motors with permanent magnets drive 14 4474 en 2011 04 e LEROY SOMER...

Page 15: ...15 Commissioning DYNEO Synchronous motors with permanent magnets drive 4474 en 2011 04 e LEROY SOMER...