R220

A.V.R.

3.3  - Electrical faults

Fault

Action

Effect

Check/Cause

No voltage at 
no load on 

start-up

Connect a new battery 

of 4 to 12 volts to 
termináis E- and E+, 

respecting the polarity, 

for 2 to 3 seconds

The alternator builds up and its 
voltage is still correct when the 
battery is removed.

- Lack of residual magnetism

The alternator builds up but its 
voltage does not reach the rated 
valué when the battery is 

removed.

- Check the connection of the voltage 
reference to the AVR
- Faulty diodes
- Armature short-circuit

The alternator builds up but its 
voltage disappears when the 

battery is removed

- Faulty AVR
- Field windings disconnected
- Main field winding open circuit - check the 
resistance

Voltage too 

low

Check the drive speed

Correct speed

Check the AVR connections (AVR may be 

faulty)

- Field windings short-circuited
- Rotating diodes burnt out
- Main field winding short-circuited - Check 

the resistance

Speed too low

Increase the drive speed
(Do not touch the AVR voltage pot. (P2)

before running at the correct speed.)

Voltage too 
high

Adjust AVR voltage 
potentiometer

Adjustment ineffective

Faulty AVR

Voltage
oscillations

Adjust AVR stability 
potentiometer

- Check the speed : possibility of cyclic 
irregularity
- Loose connections
- Faulty AVR
- Speed too low when on load (or U/F bend 
set too high)

Voltage 
correct at no 
load and too 
low when on 
load O

Run at no load and 

check the voltage 

between E+ and E- on 

the AVR

- Check the speed (or U/F bend set too high)

- Faulty rotating diodes
- Short-circuit in the main field. Check the 

resistance

- Faulty exciter armature.

(*) Caution : For single-phase operation, check that the sensing wires coming from the AVR are correctly connected to the 
operating termináis

Voltage
disappears
during
operation

Check the AVR, the 
surge suppressor, the 

rotating diodes, and 
replace any detective 

components

The voltage does not return to the 

rated valué.

- Exciter winding open circuit
- Faulty exciter armature
- Faulty AVR
- Main field open circuit or short-circuited

A

W arning  : after operational testing,  replace all access panels or covers.

i_é»rov -~

Summary of Contents for R220 VSG+CCM

Page 1: ...4291 en 10 2008 a R220 A V R Installation and maintenance ...

Page 2: ...bol for an operation capable of damaging or destroying the machine or surround ing equipment Ourtechnical support servicewiIIbe pleased to provide any additional infor mation you may require The various operations described in this manual are accompanied by recommen da tions or symbols to alert the user to potential risks of accidents It is vital that you unders tand and take notice ofthe followin...

Page 3: ... 6 4 SPARE PARTS 7 4 1 Designation 7 4 2 Technical support Service 7 All such operations performed on the A V R should be undertaken by personnel trained in the commissioning servicing and maintenance of electrical and mechanical components Copyright 2005 MOTEURS LEROY SOMER This document is the property o f MOTEURS LEROY SOMER It may not be reproduced in any form without prior authorization All b...

Page 4: ...supply sensing range 85 to 139 V 50 60 Hz Rapid response time 500 ms for a transient voltage variation amplitude of 20 Voltage setting P1 Stability setting P2 Power supply protected by 8 Atuse slow blow action tolerates 10 Afor 10 s The fuse is impregnated in the resin therefore it can not be replaced Frequency 50 Hz with ST3 jumper 60 Hz without ST3 jumper 2 2 R220AVR option Potentiometer for rem...

Page 5: ...al potentiometer settings Plpotentiometer AVRvoltageadjustment fully anti clockwise Remótevoltage adjustment potentiometer centre position Run the alternator at its rated speed If the voltage does not increase the magnetic circuit should be remagnetized see section 3 3 Turn the AVR voltage adjustment potentiometer P1 slowly until the output voltage rated valué is obtained Adjust the stability sett...

Page 6: ...tance Speed too low Increase the drive speed Do not touch the AVR voltage pot P2 before running at the correct speed Voltage too high Adjust AVR voltage potentiometer Adjustment ineffective Faulty AVR Voltage oscillations Adjust AVR stability potentiometer Check the speed possibility of cyclic irregularity Loose connections FaultyAVR Speed too low when on load or U F bend set too high Voltage corr...

Page 7: ...he complete machine type its serial number and the information indicated on the nameplate Part numbers should be identified from the exploded views and their description in the parts list Our extensive network of service stations can dispatch the necessary parts without delay To ensure correct operation and the safety of our alternators we recommend the use of original manufacture spare parts In t...

Page 8: ...Leroy Somer Leroy Somer Electro Technique Fuzhou Co Ltd NO l Emerson Road Gaishan Cangshan district Fuzhou Fujian P R China 350026 Tel 86 591 88000922 Fax 86 591 83567185 ...

Reviews: