Maintenance and testing
22
RS4/AS-i
Leuze electronic
DEUTSCH
E
NGLISH
FRANÇAIS
IT
A
LIANO
ESPAÑOL
N
EDERLANDS
Achtung!
After a defective safety-related AS-i slave has been replaced, it is essential to check that
the new AS-i slave is functioning correctly.
6.2
Check the reliability of the safety switchoff mechanism
Checks should be carried out once a year by the officer responsible for safety to ensure
that the safety AS-i system is functioning correctly, that is to say, that the AS-i safety
monitor will effect a safety switchoff when triggered by a safety-related sensor that has
been assigned to it (e.g. RS4/AS-i).
Achtung!
For this purpose the safety AS-i slave should be activated once a year, and its switching
properties should be checked by observing the safety output data of the AS-i safety
monitor.