Electrical Connection
Leuze
electronic
78
Technical Description BCL 90
Leuze electronic
7
Electrical Connection
7.1
Overview of the Installation Steps
• Connect the BCL 90 with a Leuze connector unit MA 90 or carry out the wiring according to cus-
tomer specifications
• Carry out the connection of the data and function interfaces of the BCL in the module
• Connect the PC to the connection module (at the service interface of the BCL)
• Connect the connection module to the supply voltage
7.2
Electrical Connections and Cables
The BCL's electrical connection is comprised of two 15-pin D-Sub-HD plug connections,
one device plug and one device socket installed on the housing.
The following interfaces are connected via these connectors:
• two serial data interfaces (host interface and terminal interface)
• six switched inputs (external reading cycle as well as multifunctional inputs)
• four switched outputs (output of result status functions, for connection e.g. to the PLC)
• CAN bus (for TPC operation)
• power supply
7.2.1 Core Cross-Sections
BCL without heater
• Wire all connections with copper cables with core cross-sections of at least 0.5 mm²!
BCL with heater
• Wire the power supply connections (pin 1/pin 5) with copper cables with core cross-sections of at
least 0.75 mm² and maximum lengths of 10 m!