Electrical connection
Leuze electronic
BPS 8
59
TNT
35/7-2
4
V
7.4.3
BCL/BPS socket – connecting the BPS 8 to the MA 8-01/MA 8-02
Figure 7.10: MA 8-01/MA 8-02 – Pin assignment BCL/BPS socket
The BPS 8 is connected to the MA 8-01/MA 8-02 via the KDS S-M12-5A-M12-5x-P1-xxx
interconnection cable. The voltage supply is connected via the
PWR IN HOST/RS485
socket.
BCL/BPS (5-pin socket, A-coded)
Pin
Name
Comment
1
VIN
Supply voltage for BPS 8
aprox. +5.2VDC
2
TXD
RS 232 transmission line
3
GND
Supply voltage: 0VDC
4
RXD
RS 232 receiving line
5
SWIN/
SWOUT
Programmable switching input/output of the
BPS 8
Thread
FE
Functional earth (housing)
CAUTION
Degree of protection IP 67!
Degree of protection IP 67 is achieved only if the connectors and caps are screwed into
place!
CAUTION
Connect functional earth!
Ensure that the functional earth (FE) is connected correctly.
Fault-free operation is only guaranteed if the functional earth is connected properly.
1
2
3
4
5
RXD
VIN
GND
SWIN/SWOUT
TXD
BCL / BPS
M12 socket
(A-coded)