Configuration / device parameters
Leuze electronic
BPS 8
75
TNT
35/7-2
4
V
Preset parameter
With this parameter, a preset value can be defined which the BPS 8 outputs following a
teach event. A switching input function is defined as a teach event. After reading in the
preset, the current position value is replaced by the preset value and the position value is
now calculated and output on the basis of the preset. The preset remains stored in the
BPS 8 and remains active even following a new start. In order for the BPS 8 to again output
the position value without the preset, the Preset mode must be switched off again.
Counting direction parameter
To activate this function, the preset mode must be switched on.
The
preset value is always entered
in units of mm
, independent of the resolution setting.
The scaling factor has no effect on the static preset value.
The BPS 8 is set as follows by default:
The position value is output with
normal
counting direction. With the
inverted
counting
direction, 10,000,000mm minus the position value is output. The
Preset value
and
Offset
value
parameters can be used to influence this behavior.
Figure 8.7: Counting direction for position calculation
Parameter
Description
Value range
Default
Unit
CR
Preset
mode
Switches the preset function on
or off
1: Off
2: On
1
–
–
Memory
mode
Store data temporarily or per-
manently.
1: Permanently
2: Temporarily
1
–
–
Preset value
in [mm]
New position value after teach
event.
0 … 10,000,000
0
mm
Switching
input
Parameter
Description
Value range
Default
Unit
CR
Counting
direction
Counting direction for posi-
tion calculation.
0: Normal
1: Inverted
0
–
–
c
d
e
h
f
Counting direction "normal"
Counting direction "inverted"
Position value = tape value
Position value
Counting direction
Counting direction
1,400,000 mm
8,600,000mm (=10,000,000mm - tape value)
0 mm
10,000,000 mm
0 mm
10,000,000 mm