Configuration / device parameters
Leuze electronic
BPS 8
73
TNT
35/7-2
4
V
8.5.2
Position detection
Figure 8.6: Position detection tab
Description:
The position detection controls all settings that affect the position values.
Resolution parameter
With the
Resolution
parameter, the resolution for the position values is defined. This param-
eter also performs a rounding correction (the position value is divided by the defined value
range).
The resolution only determines the mathematical decimal value and has no effect on the
measurement accuracy.
Parameter
Description
Value range
Default
Unit
CR
Resolution
in [mm]
The parameter specifies the
resolution for the position value.
The resolution has no effect on
- Static preset
- Offset.
1: 0.01
2: 0.1
3: 1
4: 10
5: 100
6: 1,000
3
mm
–
a