Fast commissioning / operating principle
Leuze electronic
MA 258
i
17
TNT
35/7-2
4
V
Attention!
If the configuration assembly is addressed with instance 118 and length 12 in the input mask
for the generic module, all MA 258
i
parameters with the value 0 are occupied in the first
moment. All default parameters of the MA must be manually entered in the configuration
assembly. Changing the individual default values is possible at any time.
For the exact description of the assemblies for input/output and configuration, please refer
to chapter 12.6.2.
The query cycle of the input and output assemblies is subsequently defined in the
Module
properties
->
Connection
path in the
Request packet interval (RPI)
input field.
The participant is thereby defined in offline mode; the data must subsequently be transferred
to the control.
Configuration of the participant using the EDS file
From RSLogix 5000 software version 20.00 and up, proceed as follows to create the
MA 258
i
as an EtherNet participant in your system:
First, load the EDS file for the device via EDS wizard into the PLC database.
Notice!
You can find the EDS file at
After loading, select the device via the device list and enter it into the HW manager via
Drag&Drop.
Open the input dialog for setting the address and additional parameters by double-click-
ing on the device symbol and make the desired entries here.
Finally, transmit the values to the device via download.