Commissioning and configuration
Leuze electronic
MA 258
i
83
TNT
35/7-2
4
V
The following overview shows the combinations of input and output data lengths (Produced/
Consumed data size) available:
Combination
Description
Input data
Output data
Data, 4 In/4 Out
Data content with max. 2 bytes
4
4
Data, 8 In/8 Out
Data content with max. 6 bytes
8
8
Data, 12 In/12 Out
Data content with max. 10 bytes
12
12
Data, 16 In/16 Out
Data content with max. 14 bytes
16
16
Data, 20 In/20 Out
Data content with max. 18 bytes
20
20
Data, 32 In/32 Out
Data content with max. 30 bytes
32
32
Data, 64 In/64 Out
Data content with max. 62 bytes
64
64
Data, 128 In/128 Out
Data content with max. 126 bytes
128
128
Data, 240 In/240 Out
Data content with max. 238 bytes
240
240
Data, 20 In/4 Out
Data content with max. 18 /2 bytes
20
4
Data, 64 In/4 Out
Data content with max. 62 /2 bytes
64
4
Data, 20 In/8 Out
Data content with max. 18 /6 bytes
20
8
Data, 64 In/8 Out
Data content with max. 62 /6 bytes
64
8
Table 12.1:
Overview of all possible combinations of input and output data lengths