Configuring the safety sensor
Leuze electronic
RSL 410
67
Bank A1
Outputs
9.4.2 Entering administration parameters
In the CONFIGURATION menu, click the
Administration
option.
The ADMINISTRATION dialog box opens.
In the input fields, enter the device data and the project data for the configuration project.
9.4.3 Activating protective function and contactor monitoring
In the CONFIGURATION menu, click the
OSSDs
option.
The OSSDs dialog box opens.
In the FUNCTION MODE list, select the protective function of the safety sensor.
The
Protective function A
option is shown in the CONFIGURATION menu.
In the CONTACTOR MONITORING list, activate the contactor monitoring of the safety sensor:
• EDM OSSD A
Click the [Confirm] button.
9.4.4 Creating and configuring protective/warning field pairs
The changeover-capable protective/warning field pairs for the selected protective function are defined in
configuration banks. The configuration banks are shown in the navigation tree of the configuration menu
as Bank , e.g.
Bank A1
.
Creating banks
In the CONFIGURATION menu, click the
Protective function A
option.
The PROTECTIVE FUNCTION A dialog box opens.
Enter the description of the protective function in the input field.
In the CONFIGURATION menu, right-click the
Protective function A
option.
Select
Add configuration bank
.
The Add bank dialog box opens.
In the Bank list, select the number of the bank and click the [Add] button. When you have added all
banks for the protective function, click [Close].
The
Bank 1
option is shown under
Protective function A
in the CONFIGURATION menu.
Configuring banks
The resolution for hand, leg or body detection, the response time and start-up behavior of the safety sensor
and the field pair changeover for the protective/warning field pairs are configured via the banks.
In the CONFIGURATION menu, select the bank the configuration of which you want to define.
The RESOLUTION, RESPONSE TIME and START-UP BEHAVIOR dialog boxes are displayed.
In the RESOLUTION dialog box, enter the resolution and, if applicable, the maximum speed of a driv
-
erless transportation system (DTS) in the input fields.
The changeover-capable protective/warning field pairs for the selected protective function are
defined in configuration banks.
The activated contactor monitoring (EDM) is assigned to indication signal outputs IO1 and/or
IO2. These signal outputs are thus disabled for the configuration of the signal outputs.
For resolution, response time and DTS speed, select the values that you used for calculating the
safety distances and additional distances for the application assigned to the configuration bank.