Electrical connection
Leuze electronic GmbH + Co. KG
MLC 530 SPG
66
8
Electrical connection
WARNING
Faulty electrical connection or improper function selection may result in serious injury!
Ä
Only allow qualified persons (see chapter 2.2 "Necessary competencies") to perform the
electrical connection.
Ä
Make certain that the safety sensor is protected against overcurrent.
Ä
For access guarding, activate the start/restart interlock and make certain that it cannot be
unlocked from within the danger zone.
Ä
Ä
Select the safety-relevant functions for the safety sensor (see chapter 5 "Functions").
Ä
Always loop both safety-related switching outputs OSSD1 and OSSD2 into the work circuit
of the machine.
Ä
Signal outputs must not be used for switching safety-relevant signals.
NOTICE
SELV/PELV!
Ä
Acc. to EN 60204-1, the external power supply must demonstrate the ability to bridge short-
term mains failures of up to 20 ms. The power supply unit must ensure safe mains separa-
tion (SELV/PELV) and a current reserve of at least 2 A.
NOTICE
Laying cables!
Ä
Lay all connection cables and signal lines within the electrical installation space or perma-
nently in cable ducts.
Ä
Lay the cables and lines so that they are protected against external damages.
Ä
For further information: see EN ISO 13849-2, Table D.4.
NOTICE
Device connection!
Ä
Use shielded cables for device connection.
NOTICE
Reset!
Pin1 of the receiver is a clocked input and output. It is thus not possible to couple the reset sig-
nal with other devices. This can result in an erroneous, automatic reset trigger.