FIRE ZONE CHECKOUT
1. Verify that the console displays "SYSTEM OK". Check the fire zone per the sensor
manufacturer's instructions. The fire alarm should be activated.
Note:
The Controller’s Fire Alarm Verification feature, if used, will require two consecutive
activations of the sensor.
2. Cancel the alarm at the console to silence the alarm. The display should indicate that the zone is
still in alarm.
3. Arm the security system then disarm it. This arm/disarm cycle will reset the smoke detector. If
the cause for the alarm (i.e. smoke) has cleared, the display will return to "SYSTEM OK".
OUTPUT CHECKOUT
Command each voltage output individually. Verify that the correct device is activated. Verify that the
device is turned on when an ON command is issued and turned off when an OFF command is issued.
For a complete list of output unit numbers, refer to the controller Owner’s Manual that was supplied
with the system.
TROUBLE CONDITIONS
The Expansion Enclosure reports the following trouble conditions to the controller: security zone wiring
problems, AC power off, and low battery.
Excessive resistance or ground faults in the loop wiring are reported as zone trouble conditions.
AC power off is reported if the AC power has failed for more than three minutes.
The battery is checked under load periodically as requested by the controller.