www.leviton.com/evrgreen • 1-877-338-7473 • evrgreen@leviton.com
evr-green
™
Level
2 -
Network Charging Station For Public Applications
1-2
Specifications
Electrical input
Input power: 7.2 kW
Input voltage: 208/240 VAC
Input current: 30 A
Input power connections: Line 1, Line 2, Earth
recommended service panel breaker: 40A breaker double pole on dedicated circuit
recommended service panel GFCI: Do not provide external GFCI as it may conflict with internal GFCI
(CCID)
Standby power: 5 W typical
Electrical output
Output charging power: 7.2 kW
Output voltage: 240 VAC
Output current: 30 A
Output charging connector: SAE J1772
TM
EV connector on 18’ (5.48m) cable
Functional interfaces
Card reader: ISO 15693, 14443
Ground Fault detection: 20 mA CCID with auto retry (15 minute delay, 3 tries)
Plug-Out detection: Power terminated per SAE J1772
TM
specification
Power measurement: 2% @ 5 minute interval
Local Area Network: 2.4 GHz 802.15.4 dynamic mesh network
Wide Area Network: Commercial CDMA or GPrS cellular data network (GPrS only in Canada.)
Safety and operational ratings
Safety compliance: UL listed for USA and cUL certified for Canada; UL-2231-1; UL-2331-2; UL 2594;
UL1998; UL991; NEC Article 625 compliant
Surge protection: 6 kV @ 3000 A. In geographic areas subject to frequent thunder storms,
supplemental surge protection at the service panel is recommended.
EMI compliance: FCC Part 15 Class A
Operating temperature: -22°F to 131°F (-30°C to +55°C)
Operating humidity: Up to 95% non-condensing
Enclosure: NEMA 3r per NEMA 250-1997
Terminal block temperature rating: 212°F (100°C)
Maximum number of charging stations per radio group: 24, including gateway (each station must
be within 150 feet line-of-sight of at least one other station)