background image

c.

  Connect the 

phase wires (G)

neutral (H)

 and 

ground (I)

 conductors to appropriate 

terminals and torque to spec in the terminations table 

(fig. 4 or 5)

d.

  If installing with a 

main circuit breaker (J)

, also install 

terminal covers (L)

 that 

have been provided 

(fig. 6)

.

e.

  When installing this enclosure as the service entrance, the 

bonding strap (M)

 

(included) 

MUST

 

BE

 installed 

(fig. 7)

. Torque to 20 lb-ins.

f. 

  When installing this enclosure as a sub panel, 

DO NOT

 install the 

bonding strap (M)

NOTE: 

For Service Equipment, apply “SERVICE DISCONNECT” label (provided) to 

trim, near main breaker handle.

NOTE: 

For Branch Equipment, apply “MAIN” label (provided) to trim, near main 

breaker handle.

Step 4: Branch Circuit Breakers

WARNING: 

Leviton

 circuit breakers 

MUST BE

 used with a 

Leviton

 circuit 

breaker enclosure.

a.

  Strip and connect the load power and load neutral wires to the 

load terminals (N) 

and ground wire to the 

ground bus (O)

 of the circuit breaker enclosure 

(fig. 8)

Strip wires and torque load terminals to spec in the terminations table.

NOTE: 

Ensure that the main breaker is in the OFF position before installing any 

branch circuit breakers.

NOTE: 

Ensure that all branch circuit breakers are in the OFF position before 

installing into the panel.

WARNING:

 TO AVOID RISK OF FIRE, check all wiring and ensure all circuit breakers 

are installed in the proper position before energizing panel.

b.

  Align the 

hooks and guides (Q)

 of the branch circuit breaker with the panel and 

press until breaker snaps into place 

(fig. 9)

Step 5: Installing Cover

 (Sold separately)

a.

  Remove the 

main breaker knockout (R)

 if a main breaker was installed. Do not 

remove in installations using the 

main lugs (K)

.

b.

  

Twist-outs (S)

 must be removed for each position that contains a branch circuit 

breaker.

c.

  To remove 

twist-outs (S)

, first strike with a screwdriver, then twist with pliers until 

detached 

(fig. 10)

.

NOTE: 

Fill any unused open spaces in cover using filler plates  

(see filler plate instructions)

.

d.

 Install door using the cover screws (provided).

e.

  

Leviton

 covers contain a feature for adjustment in flush mounting applications. 

In flush mount applications for covers larger than 42 spaces, dead front interlock 
tabs MUST BE disengaged to allow for adjustment of dead front position

(fig.11a)

Turn each 

adjustment screw (T)

 until the cover fits tightly against the circuit 

breakers 

(fig.11b)

.

f.

    Apply circuit directory labels in the appropriate location depending on  

cover/door type.

Step 6: Complete the Installation

WARNING: 

Before providing power to the load center, check all electrical connections 

and confirm that the wiring is correct.

a.

  Ensure that the main and all branch circuit breakers are in the OFF position. To 

energize, first turn ON the main breaker, and then turn ON each individual branch 
circuit breaker.

SAVE THESE INSTRUCTIONS

For Technical Assistance Call: 1-800-824-3005 (USA Only)  

or 1-800-405-5320 (Canada Only) www.leviton.com

PK-A3214-10-00-0D

© 2019 Leviton Mfg. Co., Inc.

Fig. 4

Fig. 5

Fig. 6

Fig. 7

Fig. 10

Fig. 9

Fig. 11

TERMINATIONS

Termination  

Point

Wire  

Gauge

Strip  

Length

Torque

Main Breaker  
or Main Lug

   300 MCM - #3 AWG 

1.0 in.

250 lb-ins.

Main Neutral

   300 MCM - #3 AWG

1.5 in.

375 lb-ins.

Main Ground

   2/0 AWG - #4 AWG 

0.75 in.

50 lb-ins.

Load Power  
(brass)

   #4 AWG - #8 AWG  
   #10 AWG - #14 AWG 

0.40 in. 
0.40 in.

45 in-lbs. 
35 in-lbs.

Load Neutral  
(silver)

   #4 AWG - #8 AWG 
   #10 AWG - #14 AWG 

0.40 in. 
0.40 in.

45 in-lbs. 
35 in-lbs.

Ground Bus

   #4 AWG - #6 AWG 
   #8 AWG 
   #10 AWG - #14 AWG

0.50 in. 
0.50 in. 
0.50 in.

35 in-lbs. 
25 in-lbs. 
20 in-lbs.

Main Neutral (H)

Main Ground 

(I)

Phase wires 

(G) (x2)

Main lugs (K) (x2)

Main Circuit breaker (J)

Main Neutral

(H)

Main Ground 

(I)

Phase wires 

(G) (x2)

Terminal covers (L) 

(x2)

Main Circuit breaker (J)

a.

a.

b.

b.

Align hooks 

and guides (Q)

Press until 

breaker snaps 

into place

Fig. 8

Load terminals (N)

Ground

bus 

(O)

Load Power

Load Neutral

Twist-outs

(S)

Main 

breaker 

knockout

(R)

Adjustment 

screws 

(T) (x2)

Bonding strap

(M)

6 Tab locations

shown  by arrows

Tabs must be 

disengaged to  

achieve flush surface

Tabs flushed

WEB 

VERSION