background image

0-10VDC RF Wall Dimmer

Cat. No. ZS057-D0Z, Ratings: 120-277VAC, 50/60Hz.

Cat. No. ZS057-30Z, Ratings: 347VAC, 50/60Hz.

INSTALLATION INSTRUCTIONS

ENGLISH

DI-000-ZS057-02B-X1

Before Installation

• Install into any single gang device back box.  

• Support Multi-gang installations.

• Require Decora

®

 faceplate, sold separately.

•  Devices use 0-10Vdc low voltage control wires which may be installed as Class 1 or Class 2.  

IMPORTANT NOTE:

 If installed as Class 2, all devices in the circuit must be Class 2 rated and this switch must be wired per instructions below.

Class 2 Installation:

As required under NEC code NFPA 70, paragraph 725.136 (d), the Class 2 0-10V (gray and violet) control wires must be mechanically separated from 

Class 1 wiring (line, neutral and ground power lines) when located within the same electrical box.  This is accomplished by installing a mechanical barrier 

such as silicone tubing or other non-conducting sleeve over the length of 0-10V control wires.
When product is used with 

120VAC

 power source and the 0-10V control wires are connected to CL3, CL3R or CL3P rated control cables (or permitted 

substitute), then silicone tubing or other non-conducting sleeve is required over the control wires for the entire wire length from the device to the location 

where the wires exit the box.  Tubing 

is not

 required on the CL3, CL3R or CL3P between the wire connector and extending out of the electrical box.

When used with 

277VAC 

power source and the 0-10V control wires are connected to CL3, CL3R or CL3P rated control cables (or permitted substitute), 

then silicone tubing or other non-conducting sleeve is required over the control wires for the entire wire length from the device to the location where the 

wires exit the box.  Tubing 

is also

 required on the CL3, CL3R or CL3P between the wire connector and extending out of the electrical box.

NOTE:

• Silicone tubing should be NRTL (UL/CSA/ETL) recognized or equivalent to provide mechanical separation equal to .25” in air. 

• Connectors joining 0-10V control wires should be approved LISTED CONNECTORS.

• Wire connectors and wire tubing should be provided by the installation contractor.

WARNINGS

•  

TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT 

BREAKER OR FUSE AND TEST THAT POWER IS OFF BEFORE WIRING!

•  To be installed and/or used in accordance with appropriate electrical codes 

and regulations.

•  If you are unsure about any part of these instructions, consult an electrician.

CAUTIONS

•  Use this device with 

copper or copper clad wire only.

•  For indoor applications only.

•  Save these instructions.

DI-000-ZS057-02B-X1

© 2019 Leviton Mfg. Co., Inc.

To release, push sides.

Line up and press in to attach.

WARNING

TO AVOID FIRE, SHOCK, OR DEATH; 

TURN OFF POWER at circuit breaker or fuse and 

test that power is off before wiring!

1.

 

Strip wires 3/4" and connect as per wiring diagram.  

Ensure wires are firmly attached and there is no 

exposed copper.

Installation

2.

 

Gently place the wires and your device into the wall box and attach 

with screws provided.

 

3.

 

Restore power and test ON/OFF operation. LED locator light should 

be ON when switch power is turned OFF.

4.

 

If desired, change switch color.

5.

 

Install Decora faceplate.

0-10 VDC

Ballast/LED Driver

Black

Blue

Black

Hot (Black)

Gray

Neutral (White)

Line

Electrical Box

White

White

Sleeve

Violet

Connectors

Green

Ground

Class 1 installation shown (for Class 2, refer to notes)

White

Load

Neutral

Line (Hot)

Ground

Blue

Green

Violet

Gray

Black

Reviews: