CAUTIONS
• Use this device with
copper or copper clad wire only.
• For indoor applications only.
•
SAVE THESE INSTRUCTIONS.
0-10 VDC
Ballast/LED Driver
Black
Blue
Black
Hot (Black)
Gray
Neutral (White)
Line
Electrical Box
White
White
Sleeve
Violet
Connectors
Green
Ground
RF Wireless Load Control 20A Switching Relay,
RF Wireless Load Control 0-10V Dimmer
and RF Wireless Load Control 800W Dimmer
Cat. Nos. LU20S, LU107 and LU04P
INSTALLATION INSTRUCTIONS
ENGLISH
PK-A3314-10-00-2A-X3
Before Installation
• Install to outside or inside of junction box or outside of luminaire.
• If mounted inside, a plastic cover must be used (metal will limit the RF signal).
• LU107 uses 0-10Vdc low voltage control wires which may be installed as Class 1
or Class 2.
NOTE
(LU107): 0-10V Control Wiring - Connect the violet wire to the + 0-10V line
and the gray wire to the 0-10V common using Class 1 or Class 2 wiring methods
as indicated in these instructions, ballast/fixture/driver instructions or ballast/fixture/
driver label markings. Observe all requirements of any authority having jurisdiction
with respect to wire type, sleeving, isolation methods, and the like.
WARNINGS
•
TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT
BREAKER OR FUSE AND TEST THAT POWER IS OFF BEFORE WIRING!
• To be installed and/or used in accordance with appropriate electrical codes
and regulations.
• If you are unsure about any part of these instructions, consult an electrician.
PK-A3314-10-00-2A-X3
© 2019 Leviton Mfg. Co., Inc.
2
.
Strip wires 3/4 in and connect as per wiring diagram. Ensure wires are firmly
attached and there is no exposed copper.
a. LU107 Wiring Diagram
Product Description
The Leviton Lumina
®
RF Load Controllers are components within a Lumina RF
Standalone Platform and must be paired with a Lumina
®
RF Room Controller.
The LU20S contains a power supply and a 20A relay to provide remote control
switching of lighting, motor loads, and plug load control. The LU107 Load Controller
is designed for 0-10V dimming loads and to be used for individual or groups of
luminaires up to 10A. The LU04P supports individual or groups of luminaires with
phase cut dimming of loads up to 800W.
Lumina
®
RF devices communicate with each other via 2.4 GHz radio frequency.
Each wireless device in the system is designed to act as a repeater and will re-
transmit the RF signal from one device to another to ensure the signal is received by
its intended device. There are several basic system components:
• Lumina
®
RF SA App: Bluetooth
™
-enabled, wirelessly communicates with the Room
Controller to configure the system.
• Lumina
®
RF Room Controllers: these are used to coordinate and control all of the
wireless devices in a specified space or room. It manages all energy management
functionality both as required by code and as desired by the user. Contains
a Bluetooth radio to connect to mobile device with the Lumina
®
RF SA App.
Provides dimming, switching, and scene control.
• Lumina
®
RF Load Controllers: controls individual or groups of fixtures or
receptacles for plug load control. Allows for wireless dimming and ON/OFF control
of fixtures or receptacles.
• Lumina
®
RF Switches and Dimmers: provide ON/OFF, 0-10V dimming, or Phase
Cut dimming of luminaires. Adds 3-way control of luminaires for spaces with
multiple entries.
• Lumina
®
RF Occupancy Sensors: adds occupancy or vacancy sensing to the
system.
• Lumina
®
RF Photocell: adds daylight harvesting to the system.
NOTE
: Each room requires a Room Controller.
c. LU04P Wiring Diagram
Black
Load
Hot (Black)
Black
Line
120 VAC,
60Hz
Neutral (White)
Blue
White
White
Green
Ground
4.
Using the Lumina
®
RF SA App, connect to room controller to set up device and
configure your system.
• From Factory Default, the LU107 and LU20S are in auto join mode.
• For the LU04P, press and hold the button for 7 seconds, then release the
button. The locator light will blink amber. Press and release the button without
holding. The locator light will flash green and the device will be in join mode.
• When the LU04P is added to the system by the room controller, the locator
light will blink green 3 times. If it fails to be added, the locator light will blink
red 3 times
WARNING
:
TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER
at circuit
breaker or fuse and test that power is off before wiring!
1
.
Mount the Load Control device to junction box or luminaire through
1/2 in hole or knockout and secure with provided locknut.
ATTENTION
: For LU04P, ensure the thermal pad is in contact with the metal
junction box. LU04P is not to be installed in enclosed junction box.
Installation
b. LU20S Wiring Diagram
Line
120/277VAC,
50/60Hz.
Blue
White
Hot (Black)
Black
Neutral (White)
White
Load
Green
Ground
3.
Restore power at circuit breaker or fuse.
LU04P
thermal pad
The Load Control device can be turned ON and OFF automatically when the room
controller is paired with a Lumina RF Occupancy Sensor and/or photocell for
daylighting. When configured with an occupancy sensor, the Load Control device
can be programmed for Auto ON (turns ON when occupancy is detected) or Manual
ON (turns ON when a Room Controller or switch is engaged). The Load Controllers
will turn OFF when occupancy is no longer detected.
Operation
®