background image

CAUTIONS

•  Use this device with 

copper or copper clad wire only.

•  For indoor applications only.

 

SAVE THESE INSTRUCTIONS.

0-10 VDC

Ballast/LED Driver

Black

Blue

Black

Hot (Black)

Gray

Neutral (White)

Line

Electrical Box

White

White

Sleeve

Violet

Connectors

Green

Ground

RF Wireless Load Control 20A Switching Relay, 

RF Wireless Load Control 0-10V Dimmer

and RF Wireless Load Control 800W Dimmer

Cat. Nos. LU20S, LU107 and LU04P

INSTALLATION INSTRUCTIONS

ENGLISH

PK-A3314-10-00-2A-X3

Before Installation

• Install to outside or inside of junction box or outside of luminaire.

• If mounted inside, a plastic cover must be used (metal will limit the RF signal).

• LU107 uses 0-10Vdc low voltage control wires which may be installed as Class 1 

or Class 2.

NOTE

 (LU107): 0-10V Control Wiring - Connect the violet wire to the + 0-10V line 

and the gray wire to the 0-10V common using Class 1 or Class 2 wiring methods 

as indicated in these instructions, ballast/fixture/driver instructions or ballast/fixture/

driver label markings. Observe all requirements of any authority having jurisdiction 

with respect to wire type, sleeving, isolation methods, and the like.

WARNINGS

•  

TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT 

BREAKER OR FUSE AND TEST THAT POWER IS OFF BEFORE WIRING!

•  To be installed and/or used in accordance with appropriate electrical codes 

and regulations.

•  If you are unsure about any part of these instructions, consult an electrician.

PK-A3314-10-00-2A-X3

© 2019 Leviton Mfg. Co., Inc.

2

.

Strip wires 3/4 in and connect as per wiring diagram. Ensure wires are firmly

attached and there is no exposed copper. 

a. LU107 Wiring Diagram

Product Description

The Leviton Lumina

®

 

RF Load Controllers are components within a Lumina RF 

Standalone Platform and must be paired with a Lumina

®

 

 RF Room Controller. 

The LU20S contains a power supply and a 20A relay to provide remote control 

switching of lighting, motor loads, and plug load control.  The LU107 Load Controller 

is designed for 0-10V dimming loads and to be used for individual or groups of 

luminaires up to 10A. The LU04P supports individual or groups of luminaires with 

phase cut dimming of loads up to 800W.

Lumina

®

 

 RF devices communicate with each other via 2.4 GHz radio frequency.  

Each wireless device in the system is designed to act as a repeater and will re-

transmit the RF signal from one device to another to ensure the signal is received by 

its intended device.  There are several basic system components:

•  Lumina

®

 

 RF SA App: Bluetooth

-enabled, wirelessly communicates with the Room 

Controller to configure the system.

•  Lumina

®

 

 RF Room Controllers: these are used to coordinate and control all of the 

wireless devices in a specified space or room.  It manages all energy management 

functionality both as required by code and as desired by the user.  Contains 

a Bluetooth radio to connect to mobile device with the Lumina

®

 

 RF SA App.

Provides dimming, switching, and scene control.

•  Lumina

®

 

 RF Load Controllers: controls individual or groups of fixtures or 

receptacles for plug load control.  Allows for wireless dimming and ON/OFF control 

of fixtures or receptacles.

•  Lumina

®

 

 RF Switches and Dimmers: provide ON/OFF, 0-10V dimming, or Phase 

Cut dimming of luminaires.  Adds 3-way control of luminaires for spaces with 

multiple entries.

•  Lumina

®

 

 RF Occupancy Sensors: adds occupancy or vacancy sensing to the 

system.

• Lumina

®

 

 RF Photocell: adds daylight harvesting to the system.

NOTE

: Each room requires a Room Controller.

c. LU04P Wiring Diagram

Black

Load

Hot (Black)

Black

Line

120 VAC,

60Hz

Neutral (White)

Blue

White

White

Green

Ground

4.

 

 

Using the Lumina

®

 

 RF SA App, connect to room controller to set up device and 

configure your system.

•  From Factory Default, the LU107 and LU20S are in auto join mode.
•  For the LU04P, press and hold the button for 7 seconds, then release the 

button.  The locator light will blink amber.  Press and release the button without 

holding.  The locator light will flash green and the device will be in join mode.

•  When the LU04P is added to the system by the room controller, the locator 

light will blink green 3 times.  If it fails to be added, the locator light will blink 

red 3 times

WARNING

TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER 

at circuit 

breaker or fuse and test that power is off before wiring!

1

.

  Mount the Load Control device to junction box or luminaire through 

1/2 in hole or knockout and secure with provided locknut. 

ATTENTION

: For LU04P, ensure the thermal pad is in contact with the metal 

junction box.  LU04P is not to be installed in enclosed junction box.

Installation

b. LU20S Wiring Diagram

Line

120/277VAC,

50/60Hz.

Blue

White

Hot (Black)

Black

Neutral (White)

White

Load

Green

Ground

3.

 Restore power at circuit breaker or fuse.

LU04P

thermal pad

The Load Control device can be turned ON and OFF automatically when the room 

controller is paired with a Lumina RF Occupancy Sensor and/or photocell for 

daylighting.  When configured with an occupancy sensor, the Load Control device 

can be programmed for Auto ON (turns ON when occupancy is detected) or Manual 

ON (turns ON when a Room Controller or switch is engaged).  The Load Controllers 

will turn OFF when occupancy is no longer detected.

Operation

®