background image

© 2021 Leviton Mfg. Co., Inc.

FOR CANADA ONLY

For warranty information and/or product returns, residents of Canada should contact Leviton in writing at 

Leviton Manufacturing of Canada ULC

 to the attention of the 

Quality Assurance Department, 165 Hymus Blvd, Pointe-Claire 

(Quebec), Canada H9R 1E9 or by telephone at 1 800 405-5320.

For Technical Assistance Call: 1-800-824-3005 (USA Only) or 1-800-405-5320 (Canada Only) www.leviton.com

LIMITED 3 YEAR WARRANTY AND EXCLUSIONS

Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for three years from the 

purchase date. Leviton’s only obligation is to correct such defects by repair or replacement, at its option.

 For details visit www.leviton.com or call 1-800-824-3005. 

This warranty excludes and there is disclaimed liability for labor for removal 

of this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not in 

accordance with any labels or instructions. 

There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose

, but if any implied warranty is required by the applicable jurisdiction, the duration 

of any such implied warranty, including merchantability and fitness for a particular purpose, is limited to three years. 

Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage 

to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation

. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.

Powerswitch is a trademark of Leviton Mfg. Co., Inc., registered in the U.S.A.

NOTE: DO NOT REMOVE DIN RAIL.

1.

  Remove both mounting screws securing the switch.

2.

  Insert a flathead screwdriver into switch tab 

(A)

. Gently pull tab outward, while pulling switch up, beginning with the tab side and then the opposite side.

NOTE:

 If replacing the switch component, remove switch rod by loosening set screw 

(B)

, pulling rod out of switch, and setting rod aside.

NOTE:

 If replacing the switch component, you can remove auxiliary contact on switch, by inserting flathead screwdriver tip between switch and auxiliary contact, and pressing outward.

REMOVE SWITCH

NOTE:

 If replacing the switch component, re-install switch rod, ensuring it is fully seated in bottom of pocket. Tighten set screw to 8-10 in.-lbs. (0.9-1.1 N-m).

NOTE:

 If replacing the switch component, attach auxiliary contact (if applicable) to switch, by fitting the tabs on top and pressing in the auxiliary contact in a downward motion.

1.

  Mount switch onto DIN rail by hooking back side hinge onto DIN rail, and then gently pull switch tab outward and push switch down, until it snaps into place.

2.

  Slide switch into position and align the two screw holes with threaded holes in base plate. Tighten 2 mounting screws to 6-8 in.-lbs. (0.67-0.9 N-m).

3.

  Verify switch cover properly mates with switch mechanism with cover closed, and that ON/OFF handle moves freely.

REPLACE SWITCH

Switch

mounting

screws

Flathead

screwdriver

 

Switch

tab

 

 

Switch rod set screw

A

B

MDS3-AX - SSCR Rating:

Suitable for use on a circuit capable of delivering not 

more than 10kA rms symmetrical amperes, 600V 

max., when protected by 60A, Class J fuses.

Rating

Poles

HP Rating

30/32A

2

120 VAC 1 Ø

2 HP

30/32A

2

208-240 VAC 1Ø

5 HP

30/32A

2

480 VAC 1 Ø

5 HP

30/32A

2

600 VAC 1 Ø

5 HP

30/32A

3

120/208 VAC 3 Ø

10 HP

30/32A

3

208-240 VAC 3 Ø

10 HP

30/32A

3

480 VAC 3 Ø

20 HP

30/32A

3

600 VAC 3 Ø

25 HP

Auxiliary Contact Rating

10A

1

600 VAC

Short circuit ratings at 600VAC

kA

Fuse / A

Class of fuse

10

60

J

HP Rating: 30/32A-600VAC Max.

Torque:

Switch terminals:  

7 in.-lbs. (0.8 N-m)

Neutral terminals:  

15 in.-lbs. (1.7 N-m)

Ground terminals: 

15 in.-lbs. (1.7 N-m)

Auxiliary contact*: 

7 in.-lbs. (0.8 N-m) 

*(if used)

Conductor sizes accepted:

Switch terminals: 

#14 - #8 AWG

Neutral terminals:  

#14 - #8 AWG

Ground terminals: 

#14 - #8 AWG

Auxiliary contact*: 

#18 - #14 AWG 

*(if used)

MDS3-AX, MDS3-AC, MDS3-ST, MDS3-AST

MDS6-AX - SSCR Rating:

Suitable for use on a circuit capable of delivering not 

more than 100kA rms symmetrical amperes, 600V 

max., when protected by 100A, Class J or T fuses.

Rating

Poles

HP Rating

60A

2

120 VAC 1 Ø

2 HP

60A

2

208-240 VAC 1 Ø

10 HP

60A

2

480 VAC 1 Ø

20 HP

60A

2

600 VAC 1 Ø

20 HP

60A

3

208-240 VAC 3 Ø

20 HP

60A

3

480 VAC 3 Ø

40 HP

60A

3

600 VAC 3 Ø

40 HP

Auxiliary Contact Rating

10A

1

600 VAC

Short circuit ratings at 600VAC

kA

Fuse / A

Class of fuse

100

100

J or T

HP Rating: 60A-600VAC Max.

Torque:

Switch terminals:  

18 in.-lbs. (2 N-m)

Neutral terminals:  

31 in.-lbs. (3.5 N-m)

Ground terminals: 

31 in.-lbs. (3.5 N-m)

Auxiliary contact*:  

7 in.-lbs. (0.8 N-m) 

*(if used)

Conductor sizes accepted:

Switch terminals: 

#14 - #4 AWG

Neutral terminals:  

#14 - #1/0 AWG

Ground terminals: 

#14 - #2 AWG

Auxiliary contact*:  

#18 - #14 AWG 

*(if used)

MDS6-AX, MDS6-AC, 

MDS6-ST, MDS6-AST

MDS8-AX - SSCR Rating:

Suitable for use on a circuit capable of delivering not 

more than 100kA rms symmetrical amperes, 600V 

max., when protected by 100A, Class J or T fuses.

Rating

Poles

HP Rating

80A

2

120 VAC 1 Ø

2 HP

80A

2

208-240 VAC 1 Ø

10 HP

80A

2

480 VAC 1 Ø

20 HP

80A

2

600 VAC 1 Ø

20 HP

80A

3

208-240 VAC 3 Ø

20 HP

80A

3

480 VAC 3 Ø

40 HP

80A

3

600 VAC 3 Ø

40 HP

Auxiliary Contact Rating

10A

1

600 VAC

Short circuit ratings at 600VAC

kA

Fuse / A

Class of fuse

100

100

J or T

HP Rating: 80A-600VAC Max.

Torque:

Switch terminals:  

18 in.-lbs. (2 N-m)

Neutral terminals:  

31 in.-lbs. (3.5 N-m)

Ground terminals: 

31 in.-lbs. (3.5 N-m)

Auxiliary contact*:  

7 in.-lbs. (0.8 N-m) 

*(if used)

Conductor sizes accepted:

Switch terminals: 

#14 - #4 AWG

Neutral terminals:  

#14 - #1/0 AWG

Ground terminals: 

#14 - #2 AWG

Auxiliary contact*:  

#18 - #14 AWG 

*(if used)

MDS8-AX, MDS8-AC

MDS1-AX - SSCR Rating:

Suitable for use on a circuit capable of delivering not 

more than 65kA rms symmetrical amperes, 600V 

max., when protected by 100A, Class J fuses.

Rating

Poles

HP Rating

100A

2

110-120 VAC 1 Ø

7.5 HP

100A

2

220-240 VAC 1 Ø

20 HP

100A

2

277 VAC 1 Ø

25 HP

100A

2

440-480 VAC 1 Ø

30 HP

100A

3

550-600 VAC 3 Ø

30 HP

100A

3

110-120 VAC 3 Ø

15 HP

100A

3

220-240 VAC 3 Ø

40 HP

100A

3

440-480 VAC 3 Ø

60 HP

100A

3

550-600 VAC 3 Ø

50 HP

Auxiliary Contact Rating

10A

1

600 VAC

Short circuit ratings at 600VAC

kA

Fuse / A

Class of fuse

65

100

J

HP Rating: 100A-600VAC Max.

Torque:

Switch terminals:  

27 in.-lbs. (3 N-m)

Neutral terminals:  

53 in.-lbs. (6.0 N-m)

Ground terminals: 

31 in.-lbs. (3.5 N-m)

Auxiliary contact*:  

7 in.-lbs. (0.8 N-m) 

*(if used)

Conductor sizes accepted:

Switch terminals: 

#8 - #1/0 AWG

Neutral terminals:  

#6 - #1/0 AWG

Ground terminals: 

#14 - #2 AWG

Auxiliary contact*:  

#18 - #12 AWG 

*(if used)

MDS1-AX, MDS1-AC