GENERAL INSTRUCTION GUIDE
EUROTHERM 2204 FM APPROVED LIMIT CONTROLLERS
INDUSTRIAL OVENS
TO CHANGE THERMOCOUPLE TYPE:
Press the page button until you see
ACCS
in the upper portion of display and
LIST
in the lower portion.
Press the
SCROLL
button and the display will show
CODE
in the upper portion of the display and
“
0
”
in
the lower display. Press the
UP
arrow to change the
“
0
”
to the number
“
1
”.
Press the
SCROLL
button and the display will show
GOTO
in the upper display and
OPER
in the lower
display.
Change
OPER
to
CONF
by pressing the
UP
arrow.
Press the
SCROLL
button and the display will now show
CONF
in the upper display and
“
0
”
in the
lower.
Change the
“
0
”
to a
“
2
”
using the
UP
arrow.
Press the
PAGE
button until you see
IP
in the upper display and
CONF
in the lower display.
Press the
SCROLL
button until
INPT
appears in the upper display and the thermocouple type (LEWCO,
Inc. typically uses J)
J.TC
shows in the lower display.
Press
UP
or
DOWN
arrow until desired thermocouple type is shown.
Press
SCROLL
button again the upper display will read
RNG.L
for range low. The present value will be
shown in the lower display. This value can be changed by pressing the
UP
arrow the maximum and
minimum value is limited by the type of thermocouple selected.
Press
SCROLL
button again the upper display will read
RNG.H
for range high. The present value will
be shown in the lower display. This value can be changed by pressing the
UP
arrow the maximum and
minimum value is limited by the type of thermocouple selected.
NOTE: This high and low range will determine the maximum and minimum temperature for the set point
of the alarms.
Press the
PAGE
button until upper display says
EXIT
and lower display says
NO
. Change the
NO
to
YES
instrument will cycle power and reset.