GENERAL INSTRUCTION GUIDE

 

EUROTHERM 2204 FM APPROVED LIMIT CONTROLLERS 

                                                                                                                                                                       

 

 

INDUSTRIAL OVENS 

 

TO CHANGE TEMPERATURE CONTROL RANGE: 

NOTE

: The range high value rnG.H should never be set higher than the maximum temperature of the 

oven/drum cabinet. Doing so may cause damage to the unit. Customer assumes responsibility for any 
damages caused by changing the range high limit. 

 

Press the 

PAGE

 button until you see

 

ACCS

 in the upper portion of display and

 

LIST

 in the lower portion. 

 

Press the 

SCROLL

 button and the display will show

 

CODE

 in the upper portion of the display and 

0

 in 

the lower display. Press the 

UP

 arrow to change the 

0

 to the number 

1

”.

 

 

Press the 

SCROLL

 button and the display will show 

GOTO

 in the upper display and 

OPER

 

in the lower 

display. 

 

Change 

OPER

 to

 

CONF

 

by pressing the 

UP

 arrow.  

 

Press the 

SCROLL

 button and the display will now show

 

CONF

 in the upper display and 

0

 in the 

lower. 

 

Change the 

0

 to a 

2

 using the 

UP

 arrow. 

 

Press the 

PAGE

 button until you see 

IP

 in the upper display and 

CONF

 in the lower display. 

 

Press the 

SCROLL

 button until

 you see 

rnG.H appear in the uppder display and the value will appear 

in the lower display, use the 

UP and DOWN arrows to change this to the desired temperature 

(typically 20° over the maximum temperature of the oven)

 

 

Press 

PAGE 

button until upper display says 

EXIT 

and lower display says 

NO

. Using the 

UP

 arrow 

change the 

NO 

to 

YES

 instrument will cycle power and reset.

 

 

NOTE

: 

This procedure can be repeated to change the low range 

rnG.L.

  

  This high and low range will determine the maximum and minimum temperature for the set point of the 

alarms. 

 

Summary of Contents for EUROTHERM 2204FM

Page 1: ...se devices to meet their own application requirements not limited to but including adjusting set points and setting up alarms If you do not have a manual for your controller or wish to view an online version of it please use the following link http www eurothermonline com search searchwords manuals searchsmall_4920 2204FM The 2204FM is a 1 4 DIN FM approved alarm indicator with two FM Approved for...

Page 2: ...y reset The alarm can be acknowledged by pressing the PAGE button TO CHANGE ALARM SET POINTS NOTE If set point is shown in the lower display just press the UP and DOWN arrows If it is not shown follow the instructions below Press the PAGE button 1st on the left twice The display will show AL LIST To display the type of alarm that the instrument is set for press the SCROLL button and the alarm type...

Page 3: ...the SCROLL button once and AL 1 will appear in the upper display and FSH will appear in the lower display use the UP arrow to change this to the desired alarm type FSH FSL or OFF For alarm 2 press the SCROLL button again and the upper display will read AL 2 and use the UP arrow to change this to the desired alarm type Press the PAGE button until upper display says EXIT and lower display says NO Ch...

Page 4: ...pper display and OPER in the lower display Change OPER to CONF by pressing the UP arrow button Press the SCROLL button and the display will now show CONF in the upper display and 0 in the lower Change the 0 to a 2 using the UP arrow Press the PAGE button until you see INST in the upper display and CONF in the lower display Press the SCROLL button and you will see UNITS in the upper display and F o...

Page 5: ...ss the SCROLL button until INPT appears in the upper display and the thermocouple type LEWCO Inc typically uses J J TC shows in the lower display Press UP or DOWN arrow until desired thermocouple type is shown Press SCROLL button again the upper display will read RNG L for range low The present value will be shown in the lower display This value can be changed by pressing the UP arrow the maximum ...

Page 6: ...in the upper display and OPER in the lower display Change OPER to CONF by pressing the UP arrow Press the SCROLL button and the display will now show CONF in the upper display and 0 in the lower Change the 0 to a 2 using the UP arrow Press the PAGE button until you see IP in the upper display and CONF in the lower display Press the SCROLL button until you see rnG H appear in the uppder display and...

Reviews: