PowerGATE™ Emergency Lighting Transfer Switch
Contact Lex Products:
800.643.4460 info@lexproducts.com
6
Step 2: Installation of the ELTS Enclosure
When considering the mounting location and planning the installation of the ELTS, take into account the following:
–
Depending on the number of circuits and features of your system, enclosure size will vary
• Consider the overall cabinet mounting dimensions (Height, Depth and Width) when selecting the mounting location
–
Leave adequate space around the cabinet for entry
•
You must mount the cabinet with sufficient front clearance (minimum 3 ft, 2 inches) to allow the door to open completely
–
Ensure that there is adequate space around the cabinet for conduit
• On Main Feed cabinets, the emergency feed conduit may require additional space to meet NEC bend radius requirements
–
Mount the cabinet on a load bearing wall, in a location where it will not be subject to tampering or vandalism
•
Choose a location where it will be the most likely to be secure from damage from fire, flood, or other conditions and incidents
that will require its used
• If there are any doubts about about a location’s suitability, contact Lex Technical Services
–
Do not install the cabinet inside any other electrical or confined enclosure provided
• Anchors suitable for the wall material will be required
– NOTES:
• After determining where to mount the cabinet, make sure you have adequate equipment to lift and support the cabinet in
place while securing it to the mounting location
• The cabinet has pre-drilled mounting holes in each of the 4 corners
• Secure the cabinet to the mounting location using the 7/16” diameter screws (not included)
• Anchors suitable for the wall the panel is to be mounted on will be required and are not included