PowerGATE™ Emergency Lighting Transfer Switch
Contact Lex Products:
800.643.4460 info@lexproducts.com
7
Step 3: Planning Wire Entry into the Cabinet
–
Refer to Figure 1 for recommended conduit entry locations
–
Please note that main feed and discrete feed models have different terminal block locations.
FIGURE 1
Recommended Conduit Entry Locations Into Cabinet
NOTES:
–
For ease of wiring, the product has been designed so all electrical connections terminate in the top and right side of the cabinet
– Main Feed Series Panels
• The emergency power conduit enters the top of the panel directly above the lugs marked 208 VAC Emergency Power
– Discrete Feed Series Panels
• The emergency feed conduit circuits, the normal feed circuits and the load circuits, enter the right side of the panel, close to
their respective terminal blocks
• Control, normal power sensing and options connect within the areas noted in the example diagram above
–
Do not run the control, normal power sensing, or option conductors in the same conduit used for the emergency power conductors