If there is no power at receptacles:

1. Ensure that connections are in place and tight

2.  Ensure that power source is live 

a. Activate if not on

3. Ensure that circuit breakers are ‘I/ON’

4.  If a circuit breaker trips, identify source of short circuit or overload and correct before resetting circuit breaker 

a. Check to see if the circuit is overloaded and reduce loads as needed 

b. Check for short circuits in the cabling or load device and correct as needed

5. For those receptacles that include a GFCIs:

  a. Ensure the GFCIs are set by pressing the ‘RESET’ button

6.  If a GFCI trips, identify source of current leakage and correct before resetting the GFCI 

a. Check to see if the circuit is overloaded and reduce loads as needed 

b. Check for short circuits in the cabling or load device and correct as needed

7.  If there is still no power at receptacles: 

a. Remove PDU from use 

b. Contact Lex Products for next course of action

Technical Support

Lex Products is available to help answer any product related inquiries. For any questions or technical advice, 

please call toll free 800-643-4460 or email info@lexproducts.com.

Troubleshooting Guide