Chapter 10. INSTALLATION AND WIRING
10 - 12
5) Ground LG (Power Supply Module) separately with FG (Base board).
(A) Independent grounding : BEST (B) Joint grounding : GOOD (C) Joint Grounding : Not Allowed
6) If a malfunction occurs depend on grounding point, separate FG (Base Board) with ground.
10.2.4 Cable Specifications for wiring
Cable Specifications (
㎟
)
Kinds of external connection
Minimum
Maximum
Digital Input
0.18 (AWG 24)
1.5 (AWG16)
Digital Output
0.18 (AWG24)
2.0 (AWG14)
Analog Input/Output
0.18 (AWG24)
1.5 (AWG16)
Communication
0.18 (AWG24)
1.5 (AWG16)
Main Power
1.5 (AWG16)
2.5 (AWG12)
Grounding
1.5 (AWG16)
2.5 (AWG12)