Chapter 12. TROUBLE SHOOTING
12 - 11
12.5 Error code list
Error
code
Cause
Corrective Action
Operati
on
status
STOP
LED
Flickerin
g cycle
Diagnosis time
Re-
start
mode
2
OS ROM error
Contact the servi ce center if it reactively occurs when
the power is re -applied.
Defect
0.4 sec
When power is applied
-
3
OS ROM error
"
Defect
0.4 sec
When power is applied
-
4
RTC fault
"
Defect
0.4 sec
When power is applied
-
5
Dedicated processor
fault
"
Defect
0.4 sec
When power is applied
-
6
Program memory fault
"
Defect
0.4 sec
When power is applied
-
7
Data memory fault
"
Defect
0.4 sec
When power is applied
-
10
Watch dog error due to
OS program congestion
RE-apply the power
Reset
0.4 sec
During run
Cold
20
Program memory
backup error
Replace the battery if it has error check the program
after cc-loading it, and if an error is detected replace
the CPU module
STOP
0.4 sec
When power is applied
Cold
21
Memory module defect
Check and correct the memory module mounting
condition Re-apply the power and if an error occurs,
replace the memory module
STOP
0.4 sec
When power is applied
Cold
22
Memory module
program fault
Correct the memory module program and re-operate
the system
STOP
0.4 sec
Change into the RUN
mode
Cold
23
An normal program
Re-load the program and start it
STOP
0.4 sec
Change into the RUN
mode
Cold
30
Inconsistency between
the specified modules
by parameters and the
loaded modules
Module type inconsistency error
Refer to the flags(_IO_TYER,_IO_ DEER_N,
_IO_TYER [n]) and correct the incorrective slot, and re-
start the system
STOP
0.4 sec
Change into the RUN
mode
Cold
31
Module dismounting or
additional mounting
during run
Module mounting/ dismounting error
Refer to the flags(_IO_DEER,_IO_ DEER_N,
IO_
DEER [n]) and correct the in corrective slot, and re-
start the system
STOP
0.4 sec
When scan completes
Cold
32
Fuse disconnection
during run
Fuse disconnection error
Refer to the flags(_FUSE_ER,_FUSE _ER_N,
FUSE_ER[n]) and correct the in corrective slot, and re-
start the system
STOP
0.4 sec
When scan completes
Cold
33
Abnormal I/D module
data access during run
I/O module read/ write error
Refer to the flags(IO_RWER, _IP_RWER_N,
_IO_RWER [n]) and restart the system
STOP
0.4 sec
When scan completes
During execution of
program
cold
34
Abnormal special/ link
module data access
during run
Special/ link module interface error
Refer to the flags(_SP_IFER,_IP_ IFER_N,_IP_IFER
[n]) and restart the system
STOP
0.4 sec
When power is applied
When scan completes
During execution of
program
cold
40
During run, Scan time
over than the scan
delay time specified by
parameters
Check the scan delay time specified by parameters and
correct the parameters or the program, and then re-
start the program
STOP
0.4 sec
During execution of
program
cold
41
Unreadable instructions
in the user program
Re-load the program and re-start it
STOP
0.4 sec
During execution of
program
cold
50
External device fatal
error
Refer to the external device fatal error
flags(_ANNUN_ER,_ANC_ERR[n]) and correct the
fault devices and then re-start the system
STOP
0.4 sec
When scan completes
cold
60
The 'E-STOP' function
has been executed
Correct the program so that the error elements that
invoked the 'E_STOP' function can be eliminated in the
program and re-start the system(Cold re-start)
STOP
-
During execution of
program
cold
100
Communications
module configuration
error
If the number of computer 4communications module is
included, then adjust the maximum number with in 8
STOP
0.4 sec
When power is applied
cold
101
Special/
Communications
module initialization
failure
Adjust the number of high speed communications
modules loaded
STOP
0.4 sec
When power is applied
cold
500
Data memory backup
error
If the battery has no error
RUN
-
When power is applied
cold
501
RTC data error
If the battery has no error, re-set the time using the
GMWIN
RUN
2 sec
When power is applied
When scan completes
-
502
Lower battery voltage
Replace the battery which the power is being applied.
RUN
4 sec
When power is applied
When scan completes
-