Chapter 4. CPU module
4 - 6
3) Pulse Timer Process Time Change and Contact On/Off
If input condition turns on, output contact (Q) turns on.
The process time is newly changed when the timer function block is executed. When the process time
reaches the setting time (process time = setting time), the contact (Q) turns off.
The contact turns off after the setting time regardless of input condition off status.
The following diagram shows pulse timer timing.
4) Timer error
The maximum timer error is ‘1 scan time + time from the start of scan to execution of the timer function
block".