Chapter 7. INPUT AND OUTPUT MODULES
7- 7
7.2.6 8-points 110 VAC input module
AC Input Module
Models
Specifications
G6I-A11A
Number of input points
8 points
Insulation method
Photo coupler
Rated input voltage
100 to 120 VAC (50/60 Hz)
Rated input current
11 mA (110 VAC / 60 Hz)
Operating voltage range
85 to 132 VAC (50/60 Hz
±
3 Hz)
Maximum simultaneous input points
100%(8 points / COM) simultaneously ON
Inrush current
300 mA, 0.3 ms or lower (132 VAC)
ON voltage/ON current
80 VAC or higher / 5 mA or higher
OFF voltage/OFF current
30 VAC or lower / 2 mA or lower
Input impedance
Approx. 15 k
Ω
OFF
→
ON
15 ms or less
Response time
ON
→
OFF
25 ms or less
Common terminal
8 points/COM
Internal current consumption
60 mA
Operating indicator
LED turns on at ON state of input
External connections
9-point terminal block connector(M3
×
6 screws)
Weight
0.14 kg
G6I-A11A
00
COM
01
02
03
04
05
06
07
8
Internal
Circuit
R
R
1
07
00
9
COM
DC5V
Terminal Block Number
R
AC 110V