Chapter 7. INPUT AND OUTPUT MODULES
7- 10
7.3.2. 16-point relay output module
Relay Output Module
Models
Specifications
G6Q-RY2A
Number of output points
16 points
Insulation method
Photo coupler
Rated load voltage & current
24 VDC 2A(resistance)/point, 5 A/ COM
220 VAC 2A(COS
Ψ
= `1)/point, 5A/COM
Minimum load voltage/current
5 VDC / 1 mA
Maximum load voltage/current
250 VAC, 110 VDC
Maximum switching frequency
1200 times per hour
Surge absorber
None
Mechanical
20 million times or more
Rated load voltage/current 100000 times or more
200 VAC 1.5 A, 240 VAC 1 A (COS
Ψ
= 0.7) : 100000 times or more
200 VAC 1 A, 240 VAC 0.5 A (COS
Ψ
= 0.35) : 100000 times or more
Service life
Electrical
24 VAC 1.5 A, 100 VDC 0.1 A (L/R= 7 ms) : 100000 times or more
Off
→
On
10 ms or less
Response time
On
→
Off
12 ms or less
Common terminal arrangement
8 points/COM
Internal current consumption
415mA
Operation indicator
LED turns on at ON state of output
External connections
18-point terminal block connector (M3
×
6 screws)
Weight
0.19 kg
Wiring Diagram
00
L
01
02
03
04
05
06
07
08
L
09
0A
0B
0C
0D
0E
0F