20
OPTIONAL OPERATION
ENGLISH
Installer Setting-Remote Controller Master/Slave Setup
It is a function for settings in group control, or 2-remote controller control.
TEMP
FAN
SPEED
OPER
MODE
When pressing the button and
button simultaneously for more than 3
seconds, the system will be entered into the
installer setting mode.
- After entering into the installer setting
mode, select the ceiling height setting code
value by pressing the oper-mode button.
* Remote controller master/slave setting
code value : 07
1
Select the desired setting value with the
temperature up(
▲
), down(
▼
) button.
2
When pressing the button, currently
established static pressure value will be
set up.
3
When pressing the button and
button simultaneously for more than 3
seconds after the setting has been
completed, the setting mode will be released.
- If there isn’t any button input for more than
25 seconds, the installer setting mode will
also be released.
4
OPER
MODE
Code value
*Setting value
00:Slave
01:Master
OPER
MODE
Value
Remote controller
Function
Master
Indoor unit operates based on master remote controller at group control.
(Master is set when delivering from the warehouse.)
Slave
Setup all remote controllers except one master remote controller to slave
at group control
* Refer to the 'group control' part for details
- When controlling in groups, basic operation settings, airflow strength weak/medium/strong,
lock setting of the remote controller, time settings, and other functions may be restricted.
Summary of Contents for ABNQ18GM1A0
Page 26: ......