56
ENGLISH
FUNCTIONAL SPECIFICATIONS AC Smart BACnet
Local Definition of Object ID - The instance number is a pair, this consists of the indoor unit No. and
item.
Example of Point Table
The point table below is passed to BMS, and BMS registers the object.
Object Type
Instance Number
0
5
1
6
1
9
1
0
3
4
11
12
7
5
1
8
Device No.
(from 0 to 16)
Product Unit No.
(from 0 to 16)
Point No.
(from 0 to 16)
* Object Type (Coil : 0, Register : 4)
* Product Type (Indoor : 0, Vent : 4, AHU : 8)
** Device : Group of Product units (16EA)
Product Type
Address
Case Indoor
Function Code Device No.
Product No.
Point
Instance No.
Name
1
0
0
0
0x00000
ON/OFF status
5
0
0
0
0x00000
ON/OFF Setting
1
0
1
0
0x00010
ON/OFF status
5
0
1
0
0x00010
ON/OFF Setting
1
1
0
0
0x00100
ON/OFF status
5
1
0
0
0x00100
ON/OFF Setting
3
0
0
0
0x40000
Mode status
6
0
0
0
0x40000
Mode Setting
3
0
1
0
0x40010
Mode status
6
0
1
0
0x40010
Mode Setting
3
1
0
0
0x40100
Mode status
6
1
0
0
0x40100
Mode Setting