MODBUS PROTOCOL REGISTERS
Holding Register
Register Address
Meaning
40001
Setting for Demand control ratio (50% ~ 100%)
40002
Operation Mode Setting (0 : Cooling, 4 : Heating)
40003
Cooling Target Temperature Setting (5~20°C)
40004
Heating Target Temperature Setting (40~57°C)
40005
Control Mode Setting (On-site/Remote/Scheduled)
40006
Remote Mode Setting (Contact /Modbus)
40007
Cooling Type Setting (0 : Normal, 3 : Low Temperature)
40008
Max. Operating Frequency Setting
(0 : 120, 1 : 130, 2 : 110, 3 : 100, 4 : 90, 5 : 80, 6 : 70)
40009~40022
Reserve