161
ENGLISH
Functional Specifications ACP BACnet
Current OA Damper (Status)
3RLQWQXPEHU
Object name : CurOADamperStatus_XXX (XXX : AHU address)
Object type : Analog Input
Meaning : This object is used to monitor the current opening degree of OA damper.
3UHVHQW9DOXHSURSHUW\a
Current EA Damper (Status)
Point number : 40
Object name : CurEADamperStatus_XXX (XXX : AHU address)
Object type : Analog Input
Meaning : This object is used to monitor the current opening degree of the EA damper.
3UHVHQW9DOXHSURSHUW\a
Current MIX Damper (Status)
Point number : 41
Object name : CurMixDamperStatus_XXX (XXX : AHU address)
Object type : Analog Input
Meaning : This object is used to monitor the degree of opening of the damper current Mix.
3UHVHQW9DOXHSURSHUW\a
Cool OA Damper (Setting)
Point number : 42
Object name : OADamperCoolCommand_XXX (XXX : AHU address)
Object type : Analog Value
Meaning : This object is used to set the opening degree of OA damper cooling.
3UHVHQW9DOXHSURSHUW\a
Cool OA Damper (Status)
Point number : 43
Object name : OADamperCoolStatus_XXX (XXX : AHU address)
Object type : Analog Input
Meaning : This object is used to monitor the degree of opening of OA damper cooling that has
been set.
3UHVHQW9DOXHSURSHUW\a
Summary of Contents for ACP BACnet
Page 2: ......
Page 4: ...ii ENGLISH Explanatory Notes ...
Page 6: ...ENGLISH MEMO ...
Page 10: ...ENGLISH MEMO ...
Page 12: ...ENGLISH MEMO ...
Page 22: ...ENGLISH MEMO ...
Page 135: ...123 ENGLISH Installing ACP BACnet E may be changed ...
Page 144: ...ENGLISH MEMO ...
Page 156: ...144 ENGLISH Functional Specifications ACP BACnet ...
Page 220: ......