162
ENGLISH
Functional Specifications ACP BACnet
Cool EA Damper (Setting)
Point number : 44
Object name : EADamperCoolCommand_XXX (XXX : AHU address)
Object type : Analog Value
Meaning : This object is used to set the opening degree of the EA damper cooling.
3UHVHQW9DOXHSURSHUW\a
Cool EA Damper (Status)
Point number : 45
Object name : EADamperCoolStatus_XXX (XXX : AHU address)
Object type : Analog Input
Meaning : This object is used to monitor the degree of opening of the EA damper cooling that
has been set.
3UHVHQW9DOXHSURSHUW\a
Cool MIX Damper (Setting)
Point number : 46
Object name : MIXDamperCoolCommand_XXX (XXX : AHU address)
Object type : Analog Value
Meaning : This object is used to set the degree of opening of the MIX cooling damper.
3UHVHQW9DOXHSURSHUW\a
Cool MIX Damper (Status)
Point number : 47
Object name : MIXDamperCoolStatus_XXX (XXX : AHU address)
Object type : Analog Input
Meaning : This object is used to monitor the degree of opening of the MIX cooling damper has
been set.
3UHVHQW9DOXHSURSHUW\a
Summary of Contents for ACP BACnet
Page 2: ......
Page 4: ...ii ENGLISH Explanatory Notes ...
Page 6: ...ENGLISH MEMO ...
Page 10: ...ENGLISH MEMO ...
Page 12: ...ENGLISH MEMO ...
Page 22: ...ENGLISH MEMO ...
Page 135: ...123 ENGLISH Installing ACP BACnet E may be changed ...
Page 144: ...ENGLISH MEMO ...
Page 156: ...144 ENGLISH Functional Specifications ACP BACnet ...
Page 220: ......