27
Installation
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp.
Water Piping
rouGHING-IN
Water circuit Piping
Guidelines
1. Cap pipe to avoid dust or debris entering the piping.
2. Prior to welding or cutting of piping, check for defects. Check to see there are no slags or burrs inside pipe before installing.
3. Treat pipe threads with joint compound or Teflon tape to prevent leakage.
Gate Valve
Pressure
Gauge
Temperature
Gauge
PT Service Port
(For Cleaning
Heat Exchanger)
Gate Valve
Strainer
(50 Mesh)
Refrigerant Pipes
Water Inlet
Pipe
Water Outlet
Pipe
Water Balancing Valve
Dielectric
Pipe Union
Dielectric
Pipe Union
The Hydro Kit has a factory internally mounted Flow Switch.
Figure 18: Hydro Kit Piping Installation