Pre-coMMIssIoNING
Installer Setting Function Codes
Installer setting - function codes
Table 14 outlines the various customizable functions available to the Hydro Kit, along with their corresponding code values. Use the
actual
low/actual High comments
columns to log additional anomalies or comments related to the specific function code.
• All temperature values are stated in Fahrenheit.
• Altitude of region might impact Hydro Kit’s ability to reach stated temperatures. Unit capability is rated at sea level.
Table 14: Installer Setting - Function Codes and Parameters
function
default
Value #1
Value #2
Actual Low/Actual High
Comments
Disable 3 Minute Delay
02:01
01
-
Remote Air Sensor Connection
03:01
01 : NOT connected
02 : Connected
-
Celsius/Fahrenheit Switching
04:01
01 : Celsius
02 : Fahrenheit
-
Setting Temperature Selection
05:02
01 : Air Temperature
02 : Leaving Water Temperature
-
Auto Dry Contact
06:01
01 : Auto Start OFF
02 : Auto Start ON
-
Address Setting
07:00
00 ~ FF
-
Override Setting
08:00
00 : Slave
01 : Master
-
Water Pump Test Run
09:00
01 : Set
Zone Temperature Setpoint
(Heating Mode)
13:030:016
75 ~ 86
: Upper Limit of setting range
60 ~ 71
: Lower Limit of setting range
Leaving Water Temperature
Setpoint
(Heating Mode)
14:080:046
22 ~ 76
: Upper Limit of setting range
86 ~ 114
: Lower Limit of setting range
Setting Water
(DHW) Tank Water
Temperature Setpoint
15:080:046
122 ~ 176
: Upper Limit of setting range
86 ~ 114
: Lower Limit of setting range
Setting Outdoor Temp. Range
Water Temperature Reset
23:-10:015
50 - 68
: Upper Limit of setting range
-4 ~ 41
: Lower Limit of setting range
Setting Indoor air Temp. Range
(Weather-dependent operation)
24:021:016
68 ~ 86
: Upper Limit of setting range
60 ~ 66
: Lower Limit of setting range
Setting leaving water Temp.
(Weather-dependent operation)
25:080:046
149 ~ 176
: Upper Limit of setting range
104 ~ 129
: Lower Limit of setting range
Setting start/maintain time
(Disinfection Operation)
26:000
00 : Disable
01 : Enable
-
26:006:023
01~07 : Starting Date
(01:Sun, 02:Mon, ····, 07:Sat)
00~23 hours
: Starting Time in 24 hours
DHW Tank Temperature
Deadband Setpoint*
(Lower Limit)
27:070:010
104 ~ 129
: Maximum heating Temp.
05~60 min
: Maximum heating duration