2.1.3 Compressor stage during oil return control defrost control
■
Compressor stage at normal oil return state
2 unit combination : 60Hz + stage 2
3 unit combination : 60Hz + stage 3
■
High pressure limit
■
Low pressure limit
High pressure < 3284 kpa
High pressure
≥
3546 kpa
Pressure range
Compressor combination
Refer to combination table
Normal
Pressure range
Compressor combination
Refer to combination table
Normal
Low pressure
≥
242 kpa
Low pressure
≤
229 kpa
Function
■
Comp. combination during defrost control
Pressure limit
Normal
Before 70sec.
1 unit
2 unit
3 unit
Before 70sec.
after 70sec.
after 70sec.
1unit(half size)
minimum Hz
50 Hz
45 Hz
45 Hz +
constant comp.1
60 Hz
80 Hz
45 Hz +
constant comp.1
45 Hz +
constant comp.2
50 Hz
60 Hz
60 Hz +
constant comp.1
60 Hz +
constant comp.2
80 Hz
60 Hz +
constant comp.1
60 Hz +
constant comp.2
60 Hz +
constant comp.3